Date |
Text |
2007-12-22 10:01:53 | 2007-12-22 10:01:53 |
| |
| ** DENIEDREVIEW ** |
| |
| ** PLEASE SEE THE COMMENTS BELOW AS THERE ARE MANY |
| ITEMS WHICH ARE MISSING FROM MINIMUM CODE REQUIRED |
| DESIGN. |
| AS THERE ARE A SUBSTANTIAL AMOUNT OF ITEMS NOT SHOWN |
| FOR WHICH A REVIEW CAN NOT BE DONE AT THIS TIME. THERE |
| MAY BE NEW COMMENTS ON THE FOLLOWING REVIEW. |
| |
| 1) NOTE:PLEASE SEE THE FOLLOWING RELEVANT CODES SHALL |
| BE STATED ON PLANS FOR DESIGN. MANY OF THESE ARE SHOWN |
| HOWEVER SOME SHOWN ARE NOT YET ADOPTED BY THE STATE. |
| THESE ARE TO BE STATED ON BOTH ARCHITECTURAL AND |
| ELECTRICAL. (SOME ARE DONE ALREADY) |
| 2004 FBC W/2007 REVISIONS. |
| 2005 NFPA-70 |
| 2003 NFPA-101(SHOWS 2005) (FOR INFORMATION, THE NEXT |
| LIFE SAFETY CODE WILL BE 2006 WHEN ADOPTED) |
| 2002 NFPA-72 |
| 2003 NFPA-20 (NO YEAR SHOWN FP SHEETS) |
| |
| 2) NOTE: NOTE REMOVED |
| |
| 3) NOTE: PLEASE SEE SITE PLAN SHEET FP 2OF 5 AS THIS |
| INDICATES A SECOND *PROPOSED BUILDING* YET NO PLANS |
| WERE SUBMITTED FOR ANY NEW CONSTRUCTION. |
| PLEASE VERIFY AS IT IS THE UNDERSTANDING OF THIS |
| REVIEWER THAT THIS BUILDING ALREADY EXISTS AND WAS |
| BUILT UNDER PREVIOUS PERMIT(S). |
| PLEASE CLARIFY. |
| |
| 4) NOTE: PLEASE SEE THE LANDSCAPE PLANS DO NOT CONTAIN |
| A *RAISED SEAL* AS REQUIRED UNDER FS 481.221 |
| |
| 5) NOTE: PLEASE SEE FLORIDA BUILDING CODE CHAPTER 13. |
| PLEASE SEE SPECIFICALLY 13-415.1.ABC.1.1, .1.2 AND |
| .1.3. |
| PLANS ARE SUBMITTED WITH NO MINIMUM DESIGNS FOR THESE |
| SECTIONS OF THE FLORIDA BUILDING CODE. THESE CHANGES IN |
| CHAPTER 13 WERE ADOPTED BY THE STATE OF FLORIDA OCTOBER |
| 1ST, 2005.THE LIGHTING CONTROLS ETC WERE PART OF A |
| FEDERAL REQUIREMENT WHICH WAS PASSED IN JULY 04. PLEASE |
| KNOW AS NO LIGHTING CONTROL SYSTEM, DEVICES, |
| SCHEDULING, MAXIMUM TIMES, OVER RIDE DEVICES ETC WERE |
| SUBMITTED NO REVIEW OF THESE COULD BE DONE AT THIS |
| TIME. |
| |
| 6) NOTE: PLEASE SEE FBC 13-413.1.ABC.2.1AND 2.2 AND |
| PLACE NOTES ON PLANS ACCORDING TO THESE REQUIRED |
| SECTIONS. |
| |
| 7) NOTE: PLEASE SEE FBC 13-413.1.ABC.1.1 AND .1.2. |
| PLEASE PROVIDE WORST CASE VOLTAGE DROPS FOR BOTH |
| FEEDERS AND BRANCH CIRCUITS. |
| |
| 8) NOTE: PLEASE SEE FBC 13-415.1.AB.1, 13-415.2, |
| 13-415.1.A FOR ENERGY CALCULATIONS AND MINIMUM |
| REQUIREMENTS FOR LIGHTING POWER ALLOWANCES. |
| PLEASE SEE IN THIS CONTINUED NOTE THE INPUT DATA REPORT |
| WILL BE FURTHER NOTED AS IDR. |
| PLEASE SEE 13-415.2.ABC.1.3 AND 13-415.2.A FOR EXTERIOR |
| LIGHTING ALLOWANCES. PLEASE SEE THE IDR SHOWS A TOTAL |
| OF 12- 42W EXTERIOR LIGHT FIXTURES. HOW IS THIS |
| POSSIBLE WHEN THE PLANS SHOW SUBSTANTIALLY MORE |
| LIGHTING FIXTURES? PLEASE SEE FOR EXAMPLES: FIXTURES N, |
| M, CC, BB, AA ETC. |
| THIS IS ONLY TO NOTE A FEW. THE WATTAGES AS LISTED ON |
| THE FIXTURE LEGEND CALL FOR FIXTURES AT 100W, 400W |
| ETC. |
| PLEASE BE SURE TO GO OVER ALL LIGHTING FIXTURES ON |
| PLANS INSERT THESE INTO THE LIGHTING IDR. |
| PLEASE SEE THE COMMENT IS ALSO FOR *ALL* INTERIOR |
| LIGHTING FOR THE AMOUNT OF FIXTURES, THE WATTAGES OF |
| FIXTURES, THE TYPES OF FIXTURES AND CONTROLS. |
| HOW CAN THE CONTROL OF FIXTURES BE LISTED AS *MANUAL |
| ON/OFF* WHEN THE CODE REQUIRES ALL LIGHTING ON |
| AUTOMATED CONTROL DEVICES WHICH CAN RANGE FROM CENTRAL |
| CONTROL, OCCUPANCY SENSORS, TIMERS ETC? |
| ** PLEASE SEE NOTE #2 ABOVE AS NO LIGHTING CONTROLS |
| WERE SUBMITTED THERE ARE MANY ITEMS WHICH CAN NOT BE |
| REVIEWED AT THIS TIME. |
| |
| 9) NOTE: PLEASE SEE THE ENERGY CALCULATIONS AS |
| SUBMITTED DO NOT CONTAIN AN *ORIGINAL SIGNATURE* AS |
| REQUIRED UNDER THE FLORIDA ADMINISTRATIVE CODE |
| 61G15-23.002 AND FLORIDA STATUTES 471.025. IN FACT |
| THESE CONTAIN A RAISED SEAL OVER A PHOTO-COPIED |
| SIGNATURE WHICH IS NOT PERMITTED UNDER THESE SECTIONS |
| AS STATED. |
| PLEASE BE SURE TO COMPLETE THE INFORMATION ON THE COVE |
| PAGE FOR ADDRESS ETC ALONG WITH OWNER AGENT SIGNATURE. |
| PLEASE SEE 13-101.1.1.1, AND FS AND FAC ABOVE. |
| ONE SET HAS BEEN RETAINED BY THIS OFFICE. |
| |
| 10) NOTE: PLEASE SUBMIT THE WIND LOAD CALCULATIONS FOR |
| STRUCTURAL BUILDING REVIEW. |
| FBC 106.1.2 |
| |
| 11) NOTE: PLEASE CLARIFY AIR CONDITIONING UNIT AT THE |
| DOORWAY TO THE MAIN ELECTRICAL ROOM. IS THIS ABOVE THE |
| DOOR? |
| 110.26 |
| FBC 106.1.2 FOR ADDITIONAL INFORMATION. |
| |
| 12) NOTE: PLEASE SUBMIT COMPLETED LIGHTING |
| PHOTO-METRICS FOR ALL DESIGNATED EGRESS PATHS. PLEASE |
| SEE THIS INCLUDES ALL STAIRS AND HALLWAYS UNDER NORMAL |
| AND EMERGENCY. |
| PLEASE SEE NFPA-101 7.8.1.3, 7.9.2.1AND 7.9.2.2. PLEASE |
| SEE NO INFORMATION ON PROPOSED BATTERY BACK UP SYSTEM |
| WAS SUBMITTED. PLEASE PROVIDE MINIMUM RUN TIMES AND |
| OUTPUT UNDER EMERGENCY IF LIGHTING LUMENS LEVELS ARE |
| DECREASED. |
| PLEASE SUBMIT THE MANUFACTURES SPEC/CUT SHEETS ON |
| PROPOSED SYSTEM FOR REVIEW. 90.7, 110.3 |
| PLEASE SEE NEC 700.12F AND LIFE SAFETY CODE AS NOTED |
| ABOVE ALONG WITH SECTIONS 7.8.2, AND ALL OF 7.9.3. FAC |
| 61G15-33.004 |
| FBC 106.1.2 |
| |
| 13) NOTE: PLEASE INDICATE ALL ROOM AND AREA |
| DESIGNATIONS ON PLANS. |
| SOME AREAS FOR CODE REQUIRED REVIEW CAN NOT BE |
| DETERMINED AT THIS TIME FOR USE. |
| FBC 106.1.2, 106.3.5.1.2 FOR ADDITIONAL INFORMATION. LS |
| 101, NEC 2005 |
| |
| 14) NOTE: PLEASE SEE THERE ARE SEVERAL ELECTRICAL |
| FIXTURES/OUTLETS ETC WHICH ARE MISSING CIRCUITING. |
| PLEASE COMPLETE ALL CIRCUITING AND CORRELATE WITH PANEL |
| SCHEDULES. |
| FBC 106.1.2, 106.3.5.1.2 |
| NEC 408.4, 240.4, 310.16, 700.12F ETC |
| |
| 15) NOTE: PLEASE SEE ROOM 204 AS 110.26 APPEARS NOT TO |
| HAVE BEEN MET FOR ECB PL. |
| PLEASE BE SURE TO GO OVER ALL OTHER LOCATIONS. |
| |
| 16) NOTE: PLEASE LABEL ALL EQUIPMENT AND MAINS ON |
| PLANS. AS THE MAIN ELECTRICAL ROOM LAYOUT ON E-3.1.0 |
| DOES NOT LABEL EQUIPMENT, CODE COMPLIANCE FOR 230.70, |
| 71 AND 72 CAN NOT BE DONE AT THIS TIME. |
| |
| 17) NOTE: PLANS INDICATE *LOCK OFF* DEVICES ON SEVERAL |
| ITEMS. PLEASE KNOW *LOCK OFF* DEVICE VARY IN USE AND |
| LISTINGS. MANY OF THESE DEVICES ARE LISTED FOR |
| TEMPORARY USE ONLY AND/OR FALL OFF EQUIPMENT ONCE A |
| PANEL COVER ETC IS REMOVED. THESE WILL BE VERIFIED IN |
| FIELD. IF UPON DETERMINATION THE CORRECT DEVICES ARE |
| NOT INSTALLED PERMANENT MEANS WILL BE REQUIRED TO BE |
| INSTALLED OR ALTERNATE METHODS OF MEETING CODE WILL BE |
| REQUIRED. |
| 700.12, 110.3, 90.7 ETC |
| ** WILL BE REDLINED ON FINAL PERMITTED SET OF PLANS |
| ISSUED** |
| |
| 18) NOTE: PLEASE SEE THE LEGEND FOR FIRE ALARM DEVICES |
| ON PLANS INDICATES MINIMUM LEVELS FOR CANDELA RATINGS |
| TO BE 75CD WHICH IS WHAT IS REQUIRED PER FBC |
| 11-4.28.3(4). HOWEVER PLEASE SEE SOME CD LEVELS ARE |
| BEING SHOWN WITH LESS THAN THE MINIMUM REQUIRED FOR ADA |
| COMPLIANCE. |
| PLEASE SEE FOR EXAMPLE: CRYING ROOM. PLEASE SEE OTHER |
| POSSIBLE AREAS. |
| PLEASE SEE 11-4.28.1, .2 AND .3(4) FOR ALL DEVICES FOR |
| ADA COMPLIANCE FOR LOCATIONS AND LEVELS. |
| ** ONLY ONE EXAMPLE WAS GIVEN. |
| |
| 19) NOTE: PLANS MENTIONS POSSIBLE LIGHTNING PROTECTION |
| SYSTEM. PLEASE PLACE NOTE ON PLANS WHICH REQUIRES ANY |
| PROPOSED OR INSTALLED SYSTEM SHALL MEET NFPA-780. ( OR |
| WORDS TO THAT AFFECT) |
| |
| 20) NOTE: PLEASE SEE PLANS ARE MISSING PANEL SCHEDULE |
| FOR PANELS PL AND HL. NO REVIEW CAN BE DONE AT THIS |
| TIME FOR CIRCUITS, OVER CURRENT PROTECTION ETC |
| NEC 408.4, 310.16, 240.4 |
| |
| 21) NOTE: PLEASE SEE RISER AS RISER INDICATES PANEL L1 |
| AS A SINGLE PANEL HOWEVER ON SHEET E-5.1.0 THERE ARE |
| TWO PANELS L1. THE SECOND PANEL L1 IN NOTES MENTIONS |
| THIS IS FED FROM PANEL P1. HOW IS THIS POSSIBLE WHEN |
| RISER SHOWS ONLY ONE PANEL AND PANEL P1 ALREADY FEEDS A |
| SECTION TWO OF P1? |
| ** PLEASE COMPLETE AND CORRELATE ALL PANELS AND |
| LABELING OF PANELS. AS THERE ARE PANELS MISSING ETC |
| SOME ITEMS FOR CODE REVIEW CAN NOT BE DONE AT THIS |
| TIME. |
| |
| 22) NOTE: PLEASE SEE 210.63 AND 210.8 AS AC EQUIPMENT |
| IS MISSING NEW OR EXISTING SERVICE RECEPTACLES. |
| |
| ** PLEASE KNOW ONE SET OF ELECTRICAL PLANS ARE BEING |
| RETAINED BY THIS OFFICE ALONG WITH ONE COPY OF THE |
| ENERGY CALCULATIONS SUBMITTED. |
| |
| ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY |
| COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE |
| DO NOT HESITATE IN CONTACTING THIS OFFICE. |
| PLEASE SEE BELOW FOR CONTACT INFORMATION. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW II |
| CONSTRUCTION SERVICES DEPT. |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |
2007-12-11 17:14:04 | 1-SET IN ELECTRICAL FOR REVIEW. |