Plan Review Notes
Plan Review Notes For Permit 07110604
Permit Number 07110604
Review Stop B
Sequence Number 3
Notes
Date Text
2008-02-12 17:05:40****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.THE SHUTTER CONNECTION MOUNTING TYPE ON THE
 INSTALLATION SCHEDULE IS TO CORRELATE WITH THE ANCHOR
 CHART ON THE PRODUCT APPROVAL.IT APPEARS THAT YOU ARE
 SPECIFYING WALL MOUNT 1 FOR MOST OPENINGS, BUT THIS
 REQUIRES A CONCRETE SUBSTRATE.YOU AHVE SPECIFIED
 CONC./CBS.DOES THIS MEN CONCRETE ON THE TOP, CBS ON
 THE BOTTOM?WALL MOUNT 1 AND CEILING 5 REQUIRE
 CONCRETE SUBSTRATE.
  
 2.ADDRESSED.
  
 3.ADDRESSED.
  
 4.FROM 1ST REVIEW; YOU HAVE SPECIFIED CONC/CBS.NOTE
 THAT SOME CONNECTION TYPES, SUCH AS WALL MOUNT 1 AND
 WALL MOUNT 2, REQUIRE A CONCRETE SUBSTRATE.THIS IS
 ADVISORY ONLY; I AM ATTEMPTING TO FORESEE ISSUES WHICH
 MAY ARISE ON THE NEXT SUBMITTAL.
 2ND REVIEW; SEE ITEM 1.CONCRETE SUBSTRATE REQUIRED
 FOR WALL MOUNT 1AND CEILING 5.
  
 5.SEE SHEET 9 REGARDING MINIMUM SEPARATION TO GLASS.
 1" DOES NOT APPEAR COMPLIANT; PLEASE REVISE.