Plan Review Notes For Permit 07110604 |
Permit Number |
07110604 |
|
Review Stop |
B |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2008-02-12 17:05:40 | ****CORRECTIONS**** | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | | | FBCFLORIDA BUILDING CODE 2004 | | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING | | CODE | | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL | | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | FAC FLORIDA ADMINISTRATIVE CODE | | FSFLORIDA STATUTE | | | | 1.THE SHUTTER CONNECTION MOUNTING TYPE ON THE | | INSTALLATION SCHEDULE IS TO CORRELATE WITH THE ANCHOR | | CHART ON THE PRODUCT APPROVAL.IT APPEARS THAT YOU ARE | | SPECIFYING WALL MOUNT 1 FOR MOST OPENINGS, BUT THIS | | REQUIRES A CONCRETE SUBSTRATE.YOU AHVE SPECIFIED | | CONC./CBS.DOES THIS MEN CONCRETE ON THE TOP, CBS ON | | THE BOTTOM?WALL MOUNT 1 AND CEILING 5 REQUIRE | | CONCRETE SUBSTRATE. | | | | 2.ADDRESSED. | | | | 3.ADDRESSED. | | | | 4.FROM 1ST REVIEW; YOU HAVE SPECIFIED CONC/CBS.NOTE | | THAT SOME CONNECTION TYPES, SUCH AS WALL MOUNT 1 AND | | WALL MOUNT 2, REQUIRE A CONCRETE SUBSTRATE.THIS IS | | ADVISORY ONLY; I AM ATTEMPTING TO FORESEE ISSUES WHICH | | MAY ARISE ON THE NEXT SUBMITTAL. | | 2ND REVIEW; SEE ITEM 1.CONCRETE SUBSTRATE REQUIRED | | FOR WALL MOUNT 1AND CEILING 5. | | | | 5.SEE SHEET 9 REGARDING MINIMUM SEPARATION TO GLASS. | | 1" DOES NOT APPEAR COMPLIANT; PLEASE REVISE. |
|