2008-01-25 09:49:28 | ****CORRECTIONS**** |
| |
| SAMANTHA HILL, BUILDING PLANS EXAMINER |
| 561-805-6724 [email protected] |
| |
| FBCFLORIDA BUILDING CODE 2004 |
| FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING |
| CODE |
| FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL |
| FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 |
| FAC FLORIDA ADMINISTRATIVE CODE |
| FSFLORIDA STATUTE |
| |
| 1.THE SHUTTER CONNECTION MOUNTING TYPE ON THE |
| INSTALLATION SCHEDULE IS TO CORRELATE WITH THE ANCHOR |
| CHART ON THE PRODUCT APPROVAL. YOU'VE WRITTEN A1 AND B, |
| BUT SEE SHEET 10.AN EXAMPLE WOULD BE "WALL MOUNT 1". |
| I COULD NOT LOCATE "A1" OR "B" ANYWHERE IN THE PRODUCT |
| APPROVAL. |
| |
| 2.PLEASE SEE SHEET 11.A FACTOR OF .83 OR .78 IS TO |
| BE APPLIED TO ANCHOR SPACING IF THE EDGE DISTANCE IS |
| 3".IT DOES NOT APPEAR THAT THIS FACTOR HAS BEEN |
| APPLIED. |
| |
| 3.SEE OPENING 7.FOR A DESIGN PRESSURE OF -76.7, YOU |
| MUST USE THE 90PSF COLUMN (NOT -75).THIS IS ADVISORY |
| ONLY; I CANNOT DETERMINE CODE COMPLIANCE DUE FOR THE |
| ANCHOR SPACING SPECIFIED UNTIL ITEM 1 HAS BEEN |
| ADDRESSED. |
| |
| 4.YOU HAVE SPECIFIED CONC/CBS.NOTE THAT SOME |
| CONNECTION TYPES, SUCH AS WALL MOUNT 1 AND WALL MOUNT |
| 2, REQUIRE A CONCRETE SUBSTRATE.THIS IS ADVISORY |
| ONLY; I AM ATTEMPTING TO FORESEE ISSUES WHICH MAY ARISE |
| ON THE NEXT SUBMITTAL. |
| |
| 5.A HOLD WAS PLACED ON ANOTHER PERMIT, 07060349, |
| ISSUED TO YOUR COMPANY.A REVISION IS REQUIRED; THIS |
| ISSUE HAS BEEN DISCUSSED WITH YOUR COMPANY AND THE |
| HOMEOWNER.PLEASE SUBMIT THIS REVISION AT THIS TIME. |
| NOTE THAT THIS PERMIT WILL EXPIRE SOON (2/1/08).THIS |
| PERMIT WAS NOT REVOKED DUE TO AN AGREEMENT BETWEEN ME |
| AND YOUR COMPANY THAT A REVISION WOULD BE SUBMITTED. |
| THIS HAS NOT BEEN DONE.ALLOWING THIS PERMIT TO BE |
| REVOKED OR TO EXPIRE WILL PUT THIS PERMIT IN THE STATUS |
| OF WORK BEING DONE WITHOUT A PERMIT AND MAY BE SUBJECT |
| TO DISCIPLINARY ACTION.PLEASE ADDRESS THIS AT THIS |
| TIME. |