Plan Review Notes
Plan Review Notes For Permit 07110597
Permit Number 07110597
Review Stop E
Sequence Number 4
Notes
Date Text
2008-02-05 17:50:26REVISED SHEETS S-1, E-1 AND E-2
 SHEET S-1 WAS FOR REVISION OF ELEC ONLY, STILL NEED TO
 USE ORIGINAL PLANS FOR ANY STAMPS OR REVIEWED ITEMS
 FROM OTHER TRADES.
  
 REDLINED SHEET E-1 AS THE RISER HAS BEEN REVISED FOR
 NEW CONDUCTORS FROM MAIN TO FPL TRANSFORMER AND NOW
 SHOWS NEW *EQUIPMENT GROUNDING CONDUCTORS* FROM FPL TO
 FIRST MEANS OF DISCONNECT WHICH IS NOT PERMITTED.
 PLEASE SEE 250.6 AND 250.24 . IF THESE ARE INSTALLED
 THIS WOULD CREATE OBJECTIONABLE CURRENTS WHICH IS NOT
 PERMITTED BUT ALSO A SAFETY ISSUE WITH SERVICE. PLEASE
 REMOVE.