Plan Review Notes
Plan Review Notes For Permit 07110597
Permit Number 07110597
Review Stop E
Sequence Number 3
Notes
Date Text
2008-01-30 17:57:26** DENIED REVIEW/REVISION **
  
 1) NOTE: PLEASE SUBMIT A COMPLETE SET OF REVISED PLANS.
 PLEASE SEE THE EXISTING SHEETS S-1, E-1 STILL SHOW
 INFORMATION, LOCATIONS, AND EQUIPMENT WHICH IS NOT THAT
 OF THE EQUIPMENT ON-SITE OR THE EQUIPMENT LISTED ON
 E-2.
 PLEASE SEE THE ATS SPECIFIED ON SHEET E-2 DOES NOT
 CORRELATE WITH THAT OF THE SHEETS E-1 OR S-1 AND DOES
 NOT MATCH WITH THE MANUFACTURES SPECS/CUT SHEETS.
 PLEASE SUBMIT NEW PLANS AND NEW CUT SHEETS FOR ANY AND
 ALL CHANGES IN EQUIPMENT AND SPECS.
 110.3, 90.7 NFPA-70 2005
 FBC 106.1.2, 106.3.5.1.2
  
 2) NOTE: PLEASE COMPLETE TITLE BLOCK INFORMATION FOR
 ENGINEER OF RECORD. PLEASE SEE AFC 61G15-23.002 FOR ALL
 REQUIRED INFORMATION SUCH AS PRINTED NAME , ADDRESS,
 PHONE , LICENSE ETC
 SOME INFORMATION IS SHOWN BUT NOT ALL.
  
 ** PLEASE BE SURE TO ADDRESS COMMENTS. IF THERE ARE ANY
 QUESTIONS, ANY COMMENTS NOT TYPED IN A CLEAR MANOR OR
 NOT UNDERSTOOD IN ANYWAY PLEASE DO NOT HESITATE IN
 CONTACTING THIS REVIEWER.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  