Plan Review Notes
Plan Review Notes For Permit 07110597
Permit Number 07110597
Review Stop E
Sequence Number 2
Notes
Date Text
2007-12-20 20:04:12THE PRINTED NAME AND LICENSE # OF THE ENGINEER WAS
 STILL MISSING ON TITLE BLOCKS PER FAC 61G15-23.002
 THIS WAS WRITTEN ON SHEETS BY REVIEWER.
  
 REDLINED 702.11 AS THE DISCONNECTING MEANS TO MEET
 225.31-225.39AND 702.11 EXCEPTION SHALL BE READILY
 ACCESSIBLE, AND MEET 110.27.
  
 ONLY ONE SET OF ATS SPECS AND GEN SPECS SUBMITTED WHICH
 WERE ATTACHED TO OLD PLANS.MADE COPIES FOR 2ND SET
 AND ATTACHED TO NEW SETS.