Date |
Text |
2007-12-11 09:23:29 | DENIED |
| REFERENCE: FBC-2004 FUEL GAS |
| FBC-2004 CHAPTER 1 |
| FLORIDA ADMINISTRATIVE CODE |
| FLORIDA STATUTES |
| |
| 1. INDICATE THE CODE IN EFFECT AT THE TIME OF DESIGN. |
| (FBC-2004 W/2007 AMENDMENTS) |
| |
| 2. SHT S-1 INDICATES SHT 1 OF 2, BUT NO SHT 2 |
| SUBMITTED. PLEAE CLARIFY. SECTION 106.1.1. |
| |
| 3. SHTS S-1, E-1 & E-2 THE ENGINEER SHALL LEGIBLY |
| INDICATE THEIR NAME AND LICENSE NUMBER ON EACH SHEET. |
| FAC 61G15-23.002(2) & FS 471.025. |
| |
| 4. SHT E-2 SHALL BE SIGNED, SEALED, DATED AS REQUIRED |
| BY FLORIDA STATUTES & SECTION 106.1. |
| |
| 5. SHT S-1 INDICATE THE MEASUREMENT OFF ALL STRUCTURES |
| TO THE SIDES OF THE GENERATOR. (WALLS & BUILDING). |
| SECTION 106.1.2. |
| |
| 6. SUBMIT THE INSTALLATION INSTRUCTIONS FOR THE |
| GENERATOR SHOWING REQUIRED CLEARANCE ON ALL SIDES OF |
| THE GENERATOR FOR SERVICE ETC. SECTION 106.1.2. |
| |
| 7. THE GENERATOR SHALL BE LISTED. PLEASE SUBMIT |
| INFORMATION SHOWING REQUIRED LISTING. SECTION 301.3 |
| FUEL GAS CODE. |
| |
| 8. PLEASE INDICATE IF THE GAS METER IS A DEDICATED |
| METER FOR THE GENERATOR ONLY. IF NOT PLEASE INDICATE |
| THE TOTAL BTU LOAD ON THE SYSTEM, AND SHOW THE TOTAL |
| DEVELOPED LENGTH FOR ALL OTHER GAS LINES OFF THE METER. |
| INDICATE WHERE THE OTHER GAS LINE CONNECTS AT THE |
| METER. |
| |
| 9. GAS ISOMETRIC SHEET SHOWS A CLOCK VALVE. PLEASE |
| INDICATE WHAT A CLOCK VALVE IS AND SUBMIT MANUF. |
| SPECIFICATION FOR THE CLOCK VALVE. |
| |
| 10. GAS ISOMETRIC SHEET A SHUT OFF VALVE AND UNION ARE |
| REQUIRED IMMEDIATELY UPSTREAM OF THE REGULATOR. SECTION |
| 409.4. |
| |
| 11. THE PRINTED NAME AND SIGNATURE OF THE PERSON |
| DESIGNING THE GAS PIPING SHALL BE ON THE GAS ISOMETRIC |
| RISER DIAGRAM. SECTION 106.1.3. |
| |
| 12. SUBMIT THE MANUF SPECIFICATION SHEETS FOR THE GAS |
| REGULATOR. INDICATE THE MODEL NUMBER USED. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID |
| SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY |
| ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU |
| FOR YOUR ANTICIPATED COOPERATION. |
| |
| REVIEW BY KEN STEVENS |
| (561) 805-6721 |
| FAX (561) 805-6731 |
| E-MAIL [email protected] |