Plan Review Notes
Plan Review Notes For Permit 07110597
Permit Number 07110597
Review Stop G
Sequence Number 1
Notes
Date Text
2007-12-11 09:23:29DENIED
 REFERENCE: FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. INDICATE THE CODE IN EFFECT AT THE TIME OF DESIGN.
 (FBC-2004 W/2007 AMENDMENTS)
  
 2. SHT S-1 INDICATES SHT 1 OF 2, BUT NO SHT 2
 SUBMITTED. PLEAE CLARIFY. SECTION 106.1.1.
  
 3. SHTS S-1, E-1 & E-2 THE ENGINEER SHALL LEGIBLY
 INDICATE THEIR NAME AND LICENSE NUMBER ON EACH SHEET.
 FAC 61G15-23.002(2) & FS 471.025.
  
 4. SHT E-2 SHALL BE SIGNED, SEALED, DATED AS REQUIRED
 BY FLORIDA STATUTES & SECTION 106.1.
  
 5. SHT S-1 INDICATE THE MEASUREMENT OFF ALL STRUCTURES
 TO THE SIDES OF THE GENERATOR. (WALLS & BUILDING).
 SECTION 106.1.2.
  
 6. SUBMIT THE INSTALLATION INSTRUCTIONS FOR THE
 GENERATOR SHOWING REQUIRED CLEARANCE ON ALL SIDES OF
 THE GENERATOR FOR SERVICE ETC. SECTION 106.1.2.
  
 7. THE GENERATOR SHALL BE LISTED. PLEASE SUBMIT
 INFORMATION SHOWING REQUIRED LISTING. SECTION 301.3
 FUEL GAS CODE.
  
 8. PLEASE INDICATE IF THE GAS METER IS A DEDICATED
 METER FOR THE GENERATOR ONLY. IF NOT PLEASE INDICATE
 THE TOTAL BTU LOAD ON THE SYSTEM, AND SHOW THE TOTAL
 DEVELOPED LENGTH FOR ALL OTHER GAS LINES OFF THE METER.
 INDICATE WHERE THE OTHER GAS LINE CONNECTS AT THE
 METER.
  
 9. GAS ISOMETRIC SHEET SHOWS A CLOCK VALVE. PLEASE
 INDICATE WHAT A CLOCK VALVE IS AND SUBMIT MANUF.
 SPECIFICATION FOR THE CLOCK VALVE.
  
 10. GAS ISOMETRIC SHEET A SHUT OFF VALVE AND UNION ARE
 REQUIRED IMMEDIATELY UPSTREAM OF THE REGULATOR. SECTION
 409.4.
  
 11. THE PRINTED NAME AND SIGNATURE OF THE PERSON
 DESIGNING THE GAS PIPING SHALL BE ON THE GAS ISOMETRIC
 RISER DIAGRAM. SECTION 106.1.3.
  
 12. SUBMIT THE MANUF SPECIFICATION SHEETS FOR THE GAS
 REGULATOR. INDICATE THE MODEL NUMBER USED.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID
 SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY
 ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved