Plan Review Notes
Plan Review Notes For Permit 07110597
Permit Number 07110597
Review Stop E
Sequence Number 1
Notes
Date Text
2007-12-10 12:22:15**** DENIED ****
  
 1) NOTE: PLEASE SEE THE FOLLOWING CODES SHALL BE STATED
 ON PLANS. MAY NOT STATE *LATEST CODE*.
 PLEASE LIST THE FOLLOWING AS ADOPTED BY THE FLORIDA
 STATUTES.
 2004 FBC W/2007 REVISIONS.
 2002 NFPA-110
 2003 NFPA-101
 2005 NFPA-70
  
 2) NOTE: PLEASE KNOW BASED ON RECENT INFORMATION FROM
 THE STATE THE LICENSE WHICH MUST BE USED TO APPLY FOR
 INSTALL AND DEAL NATURAL GAS OR LP.
 PLEASE PROVIDE LICENSING FOR INSTALL/SALES OF UNIT.
 PLEASE SEE FS 527.02
  
 3) NOTE: PLEASE SEE PLANS INDICATE THE GENERATOR AS
 EXISTING IN TWO DIFFERENT LOCATIONS. PLEASE CLEARLY
 INDICATE WHERE THE NEW GENERATOR IS BEING INSTALLED.
 PLEASE SEE NFPA-110CHAPTER 7 FOR LOCATION
 INSTALLATIONS.
  
 4) NOTE: PLEASE CLARIFY THE LOADS OF THE GENERATOR.
 PLEASE SEE RISER NOTES THERE WILL BE A MANUAL TRANSFER
 SWITCH HOWEVER PLANS ALSO NOTE THERE WILL BE A AN
 AUTOMATED TRANSFER SWITCH. WHICH ONE IS BEING
 INSTALLED?
 PLEASE KNOW IF THERE ARE ANY LIFE SAFETY OR LEGALLY
 REQUIRED LOADS BEING FED FROM THIS SOURCE AS THE
 PRIMARY BACK UP, THEN ON-SITE FUEL IS REQUIRED PER
 701.11B3 AND 700.12B3.
 PLEASE KNOW IF THERE IS ANY LIFE SAFETY AND LEGALLY
 REQUIRED LOADS SERVED PLEASE SEE 700.6, 701.7 FOR
 TRANSFER EQUIPMENT
  
 5) NOTE: PLEASE SEE THE RISER IS NOW SHOWING A NEW MAIN
 DISCONNECT BEING INSTALLED ON WHAT APPEARS TO BE THE
 LINE SIDE OF THE PREVIOUS MAIN SERVICE SWITCHGEAR.
 PLEASE SEE NEC 110.9 AND SUBMIT AIC RATINGS FOR ANY NEW
 SERVICE EQUIPMENT.
 FBC 106.3.5.1.2, 106.1.2
  
 6) NOTE: PLEASE SEENOT ALL SHEETS ARE SIGNED, DATED
 AND SEALED BY THE DESIGNER OF RECORD AS REQUIRED PER FS
 471.003, 471.025
  
 7) NOTE: PLEASE COMPLETE INFORMATION ON TITLE BLOCKS
 FOR ALL SHEETS AS REQUIRED PER FAC 61G15-23.002
 PLEASE SEE MISSING PRINTED NAME AND PRINTED LICENSE
 NUMBER OF THE ENGINEER OF RECORD.
  
 8) NOTE: PLEASE SEE THE SIZING OF CONDUCTORS MAY ONLY
 USE THE 75 DEGREE COLUMN AS 110.14 ONLY CONTAINS A
 RATING FOR LUGS.
 PLEASE KNOW DE-RATING MAY BE USE 90 DEGREE COLUMN.
  
 9) NOTE: PLEASE INCLUDE CONDUCTORS FROM NEW MAIN TO
 FPL.
 230, 310.16, 240.4
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]