2008-02-26 16:43:19 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| |
| PLUMBING PLAN REVIEW: |
| DENIED 4TH TIME: |
| |
| THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH |
| THE PREVIOUS PLUMBING PLAN REVIEW COMMENTS AS WELL AS |
| THE DESIGNER'S RESPONSES FOR THE PURPOSE OF CONTINUTY. |
| NOTE: THERE WERE NO DESIGNER COMMENT RESPONSES TO THE |
| PREVIOUS PLUMBING PLAN REVIEW. |
| |
| 1. **OK** COMMENT ADDRESSED. |
| |
| 2. **OK** COMMENT ADDRESSED. |
| |
| 3. **OK** COMMENT ADDRESSED. |
| |
| 4. **OK** RESPONSE NOTED. |
| |
| 5. **OK** RESPONSE NOTED, COMMENT ADDRESSED. |
| |
| 6. **OK** COMMENT ADDRESSED. |
| |
| 7. **OK** COMMENT ADDRESSED. |
| |
| 8.AT A MINIMUM THE SANITARY RISER AND PLUMBING FLOOR |
| PLAN ON SHEET P-100 SHALL REFLECT THE FLOOR PLAN OF |
| REVISED SHEET A-105. PER FBC PLUMBING SECTION *701.1 |
| SCOPE.** |
| |
| ****NO COMMENT RESPONSE****THE RESUBMITTED SHEET |
| P-100 HAS NOT BEEN REVISED TO REFLECT THE REVISED FLOOR |
| PLAN OF SHEET A-102 AND SHEET A-105, RENOVATED SHOWROOM |
| - RESTROOM FLOOR PLAN. PLEASE CORRELATE AND CORRECT ON |
| THE NEXT RESUBMITTAL. |
| |
| ********IMPORTANT INFORMATION******** |
| WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION |
| AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A |
| TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| END OF COMMENTS: |
| |