2008-02-12 08:10:56 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| |
| PLUMBING PLAN REVIEW: |
| DENIED 3RD TIME: |
| |
| **PREVIOUS REVIEW COMMENTS** |
| |
| 1. **OK** COMMENT ADDRESSED. |
| |
| 2. **OK** COMMENT ADDRESSED. |
| |
| 3. **OK** COMMENT ADDRESSED. |
| |
| 4. **OK** RESPONSE NOTED. |
| |
| 5. **OK** RESPONSE NOTED, COMMENT ADDRESSED. |
| |
| 6. **OK** COMMENT ADDRESSED. |
| |
| 7. **OK** COMMENT ADDRESSED. |
| |
| 8. **RESPONSE NOTED, HOWEVER THIS SINK IS STILL BEING |
| INDICATED ON SHEETS A-105 "RENOVATED SHOWROOM - |
| RESTROOM FLOOR PLAN" AS WELL AS ON SHEET P-100 SANITARY |
| RISER AND PLUMBING FLOOR PLAN. IF IT IS THE INTENT TO |
| DELETE THE SINK AS IS BEING INDICATED ON REVISED SHEET |
| A-101 THEN ALL SHEETS SHALL BE CORRELATED BY DELETING |
| THE SINK. AT A MINIMUM THE SANITARY RISER AND PLUMBING |
| FLOOR PLAN ON SHEET P-100 SHALL REFLECT THE FLOOR PLAN |
| OF REVISED SHEET A-105. PER FBC PLUMBING SECTION *701.1 |
| SCOPE.** |
| |
| SHEET A-105, "HC SINK AT KITCHEN COUNTER DETAIL": THE |
| INDICATED KOHLER K-3325 WITH A BOWL DEPTH OF THE 9-3/4" |
| IS TO DEEP FOR THIS DETAIL. PER 11-4.24.4 DEPTH. EACH |
| SINK SHALL BE A MAXIMUM OF 6-1/2" (165MM) DEEP. PLEASE |
| CORRECT THIS ON THE RESUBMITTAL. |
| |
| ********IMPORTANT INFORMATION******** |
| WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION |
| AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A |
| TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| END OF COMMENTS: |
| |