2008-02-12 13:32:52 | ****CORRECTIONS**** |
| |
| SAMANTHA HILL, BUILDING PLANS EXAMINER |
| 561-805-6724 [email protected] |
| |
| FBCFLORIDA BUILDING CODE 2004 |
| FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING |
| CODE |
| FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC* |
| CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC |
| FLORIDA ADMINISTRATIVE CODE |
| FSFLORIDA STATUTE |
| |
| |
| 1.INCLUDE 2007 AMENDMENTS IN GOVERNING CODE |
| (EFFECTIVE JULY 1, 2007). |
| |
| 3RD REVIEW - PLEASE SEE SHEET A100, "CODE SUMMERY" |
| (SIC)."THESE DRAWINGS HAVE BEEN PREPARED IN |
| ACCORDANCE WITH THE 2004 FLORIDA BUILDING CODE WITH |
| 2006 AMENDMENTS . . . "PLEASE CHANGE 2006 TO 2007. |
| |
| |
| 2-5.)ADDRESSED. |
| |
| 6.SEE PLUMBING COMMENTS REGARDING TURNING SPACE AND |
| SINK, FBC11. |
| |
| 3RD REVIEW; RESPONSE LETTER STATES THAT THIS SINK WAS |
| REMOVED.SEE A105, DETAILS HC SINK AT KITCHEN COUNTER, |
| AND "RENOVATED SHOWROOM - RESTROOM FLOOR PLAN", AND |
| ALSO THE PLUMBING FIXTURE SCHEDULE.THE DETAILS SHOW A |
| KOHLER SINK (9 1/2" DEPTH), BUT MARK D SHOWS AN ELKAY |
| UNDERMOUNT SINK (7 1/2" DEEP; NOT COMPLIANT).THE SINK |
| IS TO COMPLY WITH FBC11-4.24.4, 6 1/2" MAX DEPTH.IF |
| YOU ARE REMOVING THE SINK AS STATED (AND AS SHOWN IN |
| OTHER PLACES ON THE PLAN), PLEASE REVISE THIS SHEET TO |
| REMOVE THE SINK WHICH IS CURRENTLY SHOWN.IF |
| INSTALLING A SINK, PLEASE REVISE DETAILS (AND OTHER |
| PLACES ON THE PLAN WHERE THE SINK WAS REMOVED) TO SHOW |
| A SINK COMPLIANT WITH FBC11-4.24.4. |