 APPLICATION #07110547
 ELECTRICAL PLAN REVIEW
 4508 GARDEN AVENUE
 11/29/07
 WEST PALM BEACH, FL.
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1, AND
 FOUND NONCOMPLIANT WITH THE FOLLOWING:
 ARTICLES REFERENCED ARE 2005 NEC UNLESS OTHERWISE
 NOTED, SHEET 12 OF PLAN.
  
 1} A GROUNDING ELECTRODE CONDUCTOR IS REQUIRED AT THE
 SEPARATE STRUCTURE PER 250.32, SIZED PER 250.66.
 INCLUDE ON THE RISER DIAGRAM.
  
 2} 230.70 GENERAL.
 MEANS SHALL BE PROVIDED TO DISCONNECT ALL CONDUCTORS IN
 A BUILDING OR OTHER STRUCTURE FROM THE SERVICE-ENTRANCE
 CONDUCTORS. 225.32 LOCATION. THE DISCONNECTING MEANS
 SHALL BE INSTALLED EITHER INSIDE OR OUTSIDE OF THE
 BUILDING OR STRUCTURE SERVED OR WHERE THE CONDUCTORS
 PASS THROUGH THE BUILDING OR STRUCTURE. THE
 DISCONNECTING MEANS SHALL BE AT A READILY ACCESSIBLE
 LOCATION NEAREST THE POINT OF ENTRANCE OF THE
 CONDUCTOR. THE MAIN LUG PANEL DOES NOT COMPLY.
  
 3} BATH CIRCUIT REQUIRED TO HAVE A 20 AMP RECEPTACLE
 PER 210.11(C) (3). THIS CIRCUIT IS NOT IN THE PANEL
 SCHEDULE.
  