Plan Review Notes
Plan Review Notes For Permit 07110547
Permit Number 07110547
Review Stop B
Sequence Number 1
Notes
Date Text
2007-12-13 17:00:24RESIDENTIAL ADDITION BUILDING REVIEW FIRST CHECKLIST.
 REVIEW UNDER FBC 2004 WITH 2007 REVISIONS.
  
 1- PROVIDE RECORDED NOTICE OF COMMENCEMENT AS REQUIRED
 BY SEC. 713.13 FLORIDA STATUTE.THIS DOCUMENT MAY BE
 RECORDED AT AT LATER TIME AT TIME OF PERMIT ISSUANCE.
  
 2-TWO LAYERS OF UNDERLAYMENT ARE REQUIRED WHEN ROOF
 PITCH IS 3:12. .SEC. R905.2.7 OF 2004 FLORIDA
 RESIDENTIAL CODE.ADD THESE SPECIFICATION ON PLANS.
 SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004.
  
 3- PROVIDE COMPLETE 2X STRUCTURAL BUCK DETAIL FOR SWING
 DOOR AS REQUIRED BY SEC. R613.6.1.1 OF 2004 FLORIDA
 RESIDENTIAL CODE AND BY PRODUCT APPROVAL NOA 02-1211.13
 SUBMITTED.SEC. 106.1.2CITY AMENDMENTS TO FBC 2004.
  
 4- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW.IT WAS UPDATED TO $47,126 AS REQUIRED BY SEC.
 108.3 CITY AMENDMENTS TO FBC 2004.THEREFORE OWES
 $456.93FORUPDATED VALUATION AND RADON FEES.
  
 5- PROVIDE COMPLETE INFORMATION FOR STORM SHUTTERS.
 PROVIDE INSTALLATION SCHEDULE WITH ALL INFORMATION
 COMPLETED TO VERIFY COMPLIANCE WITH PROPOSED
 INSTALLATION. SEE ATTACHED SAMPLE OF INSTALLATION
 SCHEDULE. SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004.
  
 6- PROVIDE SOIL TEST REPORT. (TWO COPIES).PLEASE MAKE
 SURE IT HAS ENGINEER'S ORIGINAL SIGNATURE AND
 ENGINEERING FIRM CERTIFICATE OF AUTHORIZATION NUMBER AS
 REQUIRED BY SEC. 61G15-23.002(2) OF FLORIDA
 ADMINISTRATIVE CODE TO AVOID UNNECESSARY DELAYS.
  
 7- SHEET 4:INFORMATION ON (BF1) EXTERIOR BEARING
 FOOTING DETAIL DOESN'T MATCH INFORMATION GIVEN ON
 TYPICAL WALL SECTION ON SHEET 9.CLARIFY THICKNESS FOR
 VISQUEEN TO BE USED. 6 MIL OR 10 MIL. REVISE AS
 REQUIRED.
  
 8- SHEET 5:
 A) REVISE REINFORCED MASONRY WALLS NOTE #1.SEE
 SEC. R606.4 OF 2004 RESIDENTIAL CODE FOR MIN.
 COMPRESSIVE STRENGTH REQUIRED.
  
 B) REVISE NOTE #9. INFORMATION ON THIS NOTE DOESN'T
 MATCH INFORMATION GIVEN ON TYP. CORNER REINFORCING OF
 BOND BEAM ON SHEET 6.REVISE AS REQUIRED.
  
 C) REVISE NOTE #11.CITE CORRECT SECTION.FBC 2004
 305.3 DOESN'T APPLY.SEE CHAPTER 6 OF 2004 FLORIDA
 RESIDENTIAL CODE AND REVISE AS REQUIRED.
  
 D) NUMBER OF MASONRY COLUMNS SHOWNAT THE ENDS OF
 GARAGE DOOR OPENINGS AND ENTRY DOOR OPENING SHOWN ON
 THE WEST WALL SIDE DON'T MATCH INFORMATION SHOWN ON
 FOUNDATION PLAN. REVISE AS REQUIRED.
  
 9- SHEET 6:
 A) 8"X8" COLUMN CORNER DETAILDOESN'T APPLY TO THIS
 JOB.TYPICAL MASONRY FILLED CELL DETAIL DOESN'T APPLY
 TO THIS JOB EITHER.THERE AE NOT EXISTING CMU WALLS.
 EVERYTHING IS NEW.PROVIDEONLY DETAILS THAT APPLY TO
 THIS JOB TO AVOID CONFLICTS.
  
 B) TYPICAL MASONRY WALL CONSTRUCTION DOESN'T APPLY
 TO THIS JOB EITHER.TYPE AOF FOUNDATION AND TYPE OF
 TIE BEAM DON'T MATCH THOSE SHOWN ON THE OTHER PLANS.
 PROVIDE ONLY DETAILS THAT APPLY TO THIS JOB TO AVOID
 CONFLICTS.
  
 10- SHEET 8: NORTH ELEVATION IS MISSING THE LINE
 SHOWING THE SETBACK WALL BEHIND. REVISE AS REQUIRED.
 SEE COMMENTS ON REVIEWED SET OF PLANS.
  
 11- SHEET 9:CLARIFY THICKNESS OF ROOF SHEATHING.
 TYPICAL WALL SECTION SECTION CALLS FOR 5/8"C.D.X.
 PLYWOOD, WHILETYPICAL TRUSS CONNECTOR DETAIL O SHEET
 10 ANDPLYWOOD NAILING DIAPHRAGMON SHEET 11 CALLS
 FOR 19/32". REVISE AS REQUIRED.
  
 12- SHEET 10:
 A) TYPICAL TRUSS CONNECTOR: REVISE ROOF SHEATHING
 NAIL TYPE (NEED 8D RING SHANK MIN.)AND SPACING,
 INCLUDING ROOF ZONE #3. SEE SEC.R803.2.3.1 OF 2004
 FLORIDA RESIDENTIAL CODE AND REVISE AS REQUIRED. ALSO,
 CLEARLY IDENTIFY ROOF ZONE 3.
  
 B) NUMBER OF NAILS SHOWN FOR SIMPSON META 14
 CONNECTORSHOWN ON TYP. TRUSS DETAIL DON'T MATCH
 NUMBER OF NAILSSHOWN ON TRUSS CONNECTOR SCHEDULE.
 REVISE AS REQUIRED.
  
 C) ALLOWABLE UPLIFT SHOWN ON TYP. TRUSS CONNECTOR
 DOESN'T MATCH THAT ONE SHOWN ON TRUSS CONNECTOR
 SCHEDULE. REVISE AS REQUIRED.
  
 D) SPECIFY CONNECTOR AT THE ENDS OF GIRDER TRUSS
 LOCATED ON THE NORTH SIDE OF THE ROOF. NONE WAS
 SPECIFIED ON THE ROOF FRAMING PLAN. SEE COMMENTS ON
 PLAN.
  
 13- SHEET 11:
 A) WIND ZONES SKETCH:ROOF ZONE 3 DOESN'T APPLY
 ONLY TO GABLE END ROOF. IT APPLIES TO HIP ROOFS AS
 WELL. REVISE AS REQUIRED. SEE FIGURE R301.2(8) OF 2004
 FLORIDA RESIDENTIAL CODE AND FIGURE 6-3 OF ASCE 7-02
 AND REVISE AS REQUIRED.
  
 B) REVISESECTION 1606.2 REFERENCED ON THE DESIGN
 CRITERIA.SEE SEC. R301 OF 2004 FLORIDA RESIDENTIAL
 CODE FOR CORRECT SECTIONS TO BE CITED AND REVISE AS
 REQUIRED.
 ***NOTE: SAME COMMENT APPLIES TO FOOTNOTES SHOWN ON
 WIND LOAD SCHEDULE.
  
 C) REVISE ROOF SHEATHING NAILING SCHEDULE. NEED TO
 SPECIFY MIN. 8D RING SHANK NAIL AND REVISE NAIL SPACING
 ON ROOF ZONE 3 AS REQUIRED BY SEC. R803.2.3.1 OF 2004
 FLORIDA RESIDENTIAL CODE.
 ***NOTE: DELETE FOOTNOTE REGARDING RING SHANK NAIL NOT
 REQUIRED FOR MEAN ROOF HEIGHT LESS THAN 25'-0".
  
 D) REVISE PLYWOOD NAILING SKETCH TO REFLECTREVISED
 INFORMATION REQUESTED ON ITEM 13(C) ABOVE.
  
 14- PRODUCT APPROVAL FOR PRECAST LINTELS NOA 03-0605.05
 EXPIRED ON 05/21/06. NEED TO PROVIDE CURRENT NOA.
 NOTE:DESIGNER OF RECORD TO REVIEW AND APPROVE IN
 WRITING PRODUCT APPROVAL AS REQUIRED BY SEC. 106.3.3
 CITY AMENDMENTS TO FBC 2004.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712