Date |
Text |
2007-11-20 11:56:19 | ****CORRECTIONS**** |
| SAMANTHA HILL, BUILDING PLANS EXAMINER |
| 561-805-6724 [email protected] |
| |
| FBCFLORIDA BUILDING CODE 2004 |
| FBC EBFLORIDA BUILDING CODE 2004 |
| EXISTING BUILDING CODE |
| FBC*CITY OF WEST PALM BEACH |
| AMENDMENTS TO THE FBC2004 |
| |
| ROOFING PERMIT; ONLY CHECKED ITEMS APPLY |
| |
| _XX_1.)EFFECTIVE OCTOBER 1, 2007, SECONDARY WATER |
| BARRIER REQUIRED FS553.844(5)(A). PROVIDE |
| INFORMATION (PRODUCT APPROVAL OR SPECIFICATIONS) TO |
| SHOW HOW YOU WILL COMPLY WITH THIS REQUIREMENT. |
| |
| INFORMATION IS AVAILABLE AT WWW.BOAF.NET. |
| |
| PLEASE NOTE THAT AN ADDITIONAL CAP SHEET CAN BE USED TO |
| COMPLY WITH THIS REQUIREMENT.FOR THE SYSTEM YOU |
| CHOSE, SYSTEM TYPE E, TAMKO MODIFIED OVER WOOD, YOU |
| HAVE HIGHLIGHTED TAM-PLY IV AS AN OPTIONAL PLY SHEET. |
| EITHER AWAPLAN VERSA-SMOOTH OR AWAPLAN VERSAFLEX CAN BE |
| USED AS THE OPTIONAL PLY SHEET AND, AS THEY ARE BOTH |
| APPROVED CAP SHEETS, CAN BE USED AS THE SECONDARY WATER |
| BARRIER IN LIEU OF TAPING THE DECK OR PROVIDING A FULL |
| DECK MODIFIED COVERING.THIS ADDITIONAL CAP SHEET CAN |
| BE USED EITHER IN ADDITION TO OR IN LIEU OF THE TAM-PLY |
| IV. |
| |
| WHEN RESUBMITTING, PLEASE SUMMARIZE THE SYSTEM YOU |
| PROPOSE BY ITEMIZING EACH PLY, INCLUDING TREATMENT OF |
| THE DECK IF YOU CHOOSE ONE OF THOSE OPTIONS AS THE |
| SECONDARY WATER BARRIER RATHER THAN AN ADDITIONAL PLY. |
| PLEASE CONTACT ME IF YOU NEED ASSISTANCE. |
| |
| ____2.)CONTRACTOR IS TO PROVIDE THE FOLLOWING |
| INFORMATION ON THE APPLICATION, SEE ATTACHED POLICY; |
| MEAN ROOF HEIGHT, ROOF PITCH, ROOF DECK TYPE, AREA OF |
| EACH ROOF TYPE |
| |
| _XX_3.)FLORIDA STATE OR LOCAL PRODUCT APPROVAL |
| REQUIRED IN ADDITION TO THE EVALUATION REPORT |
| SUBMITTED, FAC9B72.WWW.FLORIDABUILDING.ORG |
| |
| ____4.)FOR THE FLAT DECK, SELECT THE APPROVED |
| ASSEMBLY YOU ARE USING.ALSO INDICATE WHICH FASTENER |
| YOU ARE USING IF THE OPTIONS HAVE DIFFERENT PRESSURE |
| LIMITATIONS. |
| |
| _XX_5.)FOR THE FLAT DECK, SPECIFY THE ENHANCED |
| FASTENING FOR CORNER AND PERIMETER ZONES.THIS IS TO |
| BE EITHER WRITTEN ON THE PRODUCT APPROVAL OR SUBMITTED |
| ON LETTERHEAD, TWO SETS (NOT WRITTEN ON THE RESUB |
| SHEET). |
| |
| ____ 6.)ON THE TILE PRODUCT APPROVAL, INDICATE WHICH |
| METHOD OF ATTACHMENT YOU ARE USING.IF YOU SELECT FOAM |
| ADHESIVE, PRODUCT APPROVALS REQUIRED FAC9B72. |
| |
| ____ 7.)SEE PRODUCT LIMITATION #7.CALCULATIONS |
| PREPARED BY AN ARCHITECT, ENGINEER, OR REGISTERED ROOF |
| CONSULTANT REQUIRED FOR ENHANCED FASTENING. |
| |