2008-05-15 09:21:54 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & | | REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM | | BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA | | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES | | (F.S.). | | | | MECHANICAL REVISION | | *** DENIED *** | | | | 1) THE MECHANICAL PLANS NEED THE PRINTED NAME AND | | SIGNATURE OF THE PERSON RESPONSIBLE FOR THE DESIGN WITH | | CONTACT INFORMATION, AND CONTRACTOR INFORMATION IF | | APPLICABLE ON THEM, SEE W.P.B. AMEND. 106.1.3. | | | | 2)THE AIR HANDLER MODEL NUMBERS (FSM3000) LISTED ON | | THE A/C EQUIPMENT SCHEDULE COULD NOT BE FOUND ON THE | | ARI DIRECTORY WEB-SITE, PLEASE CORRECT OR SUBMIT AN ARI | | CERTIFICATE, SEE 2004 FBC 13-607.1.ABC.3.1.1. | | | | 3) SHOW THE A/C SYSTEM SEER ON THE PLAN, PER 2004 FBC | | 13-607.1.ABC.3.1.1. | | | | 4) AS THE A/C SYSTEM HAS BEEN INCREASED TO A 2.5 TON | | SYSTEM PLEASE SUBMIT COOLING LOAD CALCULATIONS, PER | | 2004 FBC 13-607.1.ABC.1. | | | | MECHANICAL PLAN REVIEW BY; | | TOM GORDON (561) 805-6729 | | E-MAIL; [email protected] |
|