2008-08-26 11:39:38NONCOMPLIANT
 REVISION DENIED
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, 2004 FBC CHAPTER 1
 AS AMENDED AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 ALL COMMENTS RELATE TO SHEET A2, UNLESS OTHERWISE
 NOTED. ALL CODE ARTICLES REFERENCED ARE 2005 NEC UNLESS
 OTHERWISE NOTED.
  
 1} THE PERMIT SET HAD AN EXISTING 200 AMP SERVICE WITH
 A DISCONNECT IN COMPLIANCE WITH 230.70(A)(1), THE NEW
 SERVICE ON THE REVISED PLANS DO NOT COMPLY WITH THAT
 ARTICLE AND INITIATES THE FOLLOWING COMMENTS.
  
 2} DUE TO THE PANEL LOCATION, A DISCONNECT IS REQUIRED
 PER 230.70, 225.32. INDICATE LOCATION ON PLAN PER
 230.72(A)(1)
  
 3} PER 110.9 AND 110.10: OBTAIN THE AVAILABLE FAULT
 CURRENT AT THE UTILITY AND CALCULATE THE SAME AT THE
 EQUIPMENT. INDICATE THE AIC RATING FOR THE EQUIPMENT IS
 EQUAL TO OR GREATER THAN THE AVAILABLE FAULT.
  
 4} PROVIDE A SITE PLAN INDICATING THE LOCATION OF ALL
 SERVICE EQUIPMENT SO THAT COMPLIANCE WITH ARTICLE 230
 CAN BE REVIEWED.
  
 5} RECEPTACLE SPACING MUST COMPLY WITH 210.52(A)(1) AND
 210.52(A)(2). 2005 NEC. SEE REVIEWED PLAN FOR
 DEFICIENCIES IN THE MASTER BEDROOM. THESE WERE REDLINED
 ON THE PERMIT SET AND NOT CORRECTTED ON THE REVISION.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  