Plan Review Notes For Permit 07110478 |
Permit Number |
07110478 |
|
Review Stop |
E |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2008-08-26 11:39:38 | NONCOMPLIANT | | REVISION DENIED | | | | THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004 | | RESIDENTIAL BUILDING CODE, 2005 NEC, 2004 FBC CHAPTER 1 | | AS AMENDED AND FOUND NONCOMPLIANT WITH THE FOLLOWING: | | | | ALL COMMENTS RELATE TO SHEET A2, UNLESS OTHERWISE | | NOTED. ALL CODE ARTICLES REFERENCED ARE 2005 NEC UNLESS | | OTHERWISE NOTED. | | | | 1} THE PERMIT SET HAD AN EXISTING 200 AMP SERVICE WITH | | A DISCONNECT IN COMPLIANCE WITH 230.70(A)(1), THE NEW | | SERVICE ON THE REVISED PLANS DO NOT COMPLY WITH THAT | | ARTICLE AND INITIATES THE FOLLOWING COMMENTS. | | | | 2} DUE TO THE PANEL LOCATION, A DISCONNECT IS REQUIRED | | PER 230.70, 225.32. INDICATE LOCATION ON PLAN PER | | 230.72(A)(1) | | | | 3} PER 110.9 AND 110.10: OBTAIN THE AVAILABLE FAULT | | CURRENT AT THE UTILITY AND CALCULATE THE SAME AT THE | | EQUIPMENT. INDICATE THE AIC RATING FOR THE EQUIPMENT IS | | EQUAL TO OR GREATER THAN THE AVAILABLE FAULT. | | | | 4} PROVIDE A SITE PLAN INDICATING THE LOCATION OF ALL | | SERVICE EQUIPMENT SO THAT COMPLIANCE WITH ARTICLE 230 | | CAN BE REVIEWED. | | | | 5} RECEPTACLE SPACING MUST COMPLY WITH 210.52(A)(1) AND | | 210.52(A)(2). 2005 NEC. SEE REVIEWED PLAN FOR | | DEFICIENCIES IN THE MASTER BEDROOM. THESE WERE REDLINED | | ON THE PERMIT SET AND NOT CORRECTTED ON THE REVISION. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLANS EXAMINER | | CITY OF WEST PALM BEACH | | 561/805-6718 |
|