Plan Review Notes
Plan Review Notes For Permit 07110478
Permit Number 07110478
Review Stop B
Sequence Number 3
Notes
Date Text
2008-06-25 10:44:452004 FBC W/2007 REVISIONS
 REVISION TO ADD EXTERIOR DOOR TO ADDITION
  
 DENIED BY BUILDING
  
 1) THE DRAWINGS ARE REQUIRED TO HAVE A TITLE BLOCK
 CONTAINING ALL OF THE INFORMATION REQUIRED BY FLORIDA
 STATUTES AND FAC 61G15-23.002.
  
 2) SUBMIT TWO SIGNED, SEALED AND DATED COPIES OF
 REVISED DRAWINGS. FBC 106.1
  
 3) IN ADDITION TO THE FLOOR PLANS, SUBMIT TWO SIGNED
 AND SEALED COPIES OF A REVISED ELEVATION SHOWING
 LOCATION OF THE NEW DOOR. FBC R301.2.1 AND DCA RULE
 9B-72.
  
 4) IN ADDITION TO THE FLOOR PLANS, SUBMIT TWO SIGNED
 AND SEALED COPIES OF A REVISED ROOF FRAMING PLAN
 SPECIFYING THE LINTEL THAT WILL BE USED ABOVE THE DOOR
 OPENING. FBC R606.8
  
 5) THE PRESSURES SPECIFIED ON THE REVISION ARE TOO LOW
 AS THE DOOR APPEARS TO BE LOCATED IN WALL ZONE 5.
 PLEASE CORRECT. FBC R301.2.1 AND FIGURE R301.2(8).
  
 6) FBC 106.3* CITY AMENDMENTS PRODUCT APPROVALS. THOSE
 PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 THE PRODUCT APPROVALS FOR THE DOOR HAS NOT BEEN
 APPROVED IN WRITING BY THE ENGINEER.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]