Plan Review Notes For Permit 07110478 |
Permit Number |
07110478 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2007-11-28 15:55:43 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & | | REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST | | PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA | | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES | | (F.S.). | | | | *** DENIED *** | | 1) ENERGY CALCULATIONS LINE 9A-1 IS CALLING FOR R4.2, | | SEE TABLE 6C-1 ON THE SECOND PAGE OF THE ENERGY CAL'S, | | THE MINIMUM INSULATION IS R-5, SEE 2004 FBC | | 13-604.1.C.1. PLEASE CORRECT. | | | | 2)ENERGY CALCULATIONS LINE 10A IS CALLING FOR R19, | | SEE TABLE 6C-1 ON THE SECOND PAGE OF THE ENERGY CAL'S, | | THE MINIMUM INSULATION IS R-30 FOR UNDER ATTIC, SEE | | 2004 FBC 13-604.1.C.1. PLEASE CORRECT. | | | | 3) THE MODEL NUMBER 113RNA035 ON THE MECHANICAL PLAN | | FOR THE A/C CONDENSER UNIT IS A INCORRECT NUMBER, SEE | | 2004 FBC 13-607.ABC.3.1.1, PLEASE CORRECT. | | | | MECHANICAL PLAN REVIEW BY; | | TOM GORDON (561) 805-6729 | | E-MAIL; [email protected] |
|