2007-11-28 15:55:43PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) ENERGY CALCULATIONS LINE 9A-1 IS CALLING FOR R4.2,
 SEE TABLE 6C-1 ON THE SECOND PAGE OF THE ENERGY CAL'S,
 THE MINIMUM INSULATION IS R-5, SEE 2004 FBC
 13-604.1.C.1. PLEASE CORRECT.
  
 2)ENERGY CALCULATIONS LINE 10A IS CALLING FOR R19,
 SEE TABLE 6C-1 ON THE SECOND PAGE OF THE ENERGY CAL'S,
 THE MINIMUM INSULATION IS R-30 FOR UNDER ATTIC, SEE
 2004 FBC 13-604.1.C.1. PLEASE CORRECT.
  
 3) THE MODEL NUMBER 113RNA035 ON THE MECHANICAL PLAN
 FOR THE A/C CONDENSER UNIT IS A INCORRECT NUMBER, SEE
 2004 FBC 13-607.ABC.3.1.1, PLEASE CORRECT.
  