2007-11-21 17:03:24 | 2004 FBC W/2007 REVISIONS |
| ADDITION |
| |
| DENIED BY BUILDING |
| |
| 1) SUBMIT A COPY OF THE PAID RECEIPT FOR THE COUNTY |
| IMPACT FEES.IF NEW SHEETS ARE SUBMITTED FOR THE ONES |
| WITH THE IMPACT FEE STAMP, THEY WILL HAVE TO BE |
| RESTAMPED OR THE OLD SHEETS WITH THE STAMPS CAN BE |
| RESUBMITTED ALONG WITH THE NEW ONES. |
| |
| 2) THE VALUE OF THE WORK ON THE PERMIT APPLICATION WAS |
| TOO LOW. IT HAS BEEN ADJUSTED BASED ON THE ICC BUILDING |
| VALUATION DATA. FEES IN THE AMOUNT OF $265.35 WHICH |
| INCLUDES RADON FEES ARE DUE. |
| |
| 3) SHOW COMPLIANCE WITH R807.1 ATTIC ACCESS . |
| IN BUILDINGS WITH COMBUSTIBLE CEILING OR ROOF |
| CONSTRUCTION, AN ATTIC ACCESS OPENING SHALL BE PROVIDED |
| TO ATTIC AREAS THAT EXCEED 30 SQUARE FEET (2.8 M 2 ) |
| AND HAVE A VERTICAL HEIGHT OF 30 INCHES (762 MM) OR |
| GREATER. |
| THE ROUGH-FRAMED OPENING SHALL NOT BE LESS THAN 22 |
| INCHES BY 30 INCHES (559 MM BY 762 MM) AND SHALL BE |
| LOCATED IN A HALLWAY OR OTHER READILY ACCESSIBLE |
| LOCATION. A 30-INCH (762 MM) MINIMUM UNOBSTRUCTED |
| HEADROOM IN THE ATTIC SPACE SHALL BE PROVIDED AT SOME |
| POINT ABOVE THE ACCESS OPENING. SEE SECTION M1305.1.3 |
| FOR ACCESS REQUIREMENTS WHERE MECHANICAL EQUIPMENT IS |
| LOCATED IN ATTICS. |
| |
| 4) SPECIFY THE SPACING OF THE VERTICAL WALL |
| REINFORCEMENT ON THE PLANS. SEE FBC R609.3. |
| |
| 5) THE CONCRETE NOTES ON D1 SPECIFY THE WRONG EDITION |
| ON ACI 318. CHAPTER 43 OF THE 2004 FBC RESIDENTIAL |
| SPECIFIES AC1 318-02. PLEASE CORRECT. |
| |
| 6) THE CLADDING PRESSURES SPECIFIED UNDER WIND |
| INFORMATION ON A1 ARE INCORRECT. SEE FBC TABLE |
| R301.2(2) AND USE THE 10 SQFT EFFECTIVE WIND AREA FOR |
| WORST CASE. |
| |
| 7) SOME OF THE ROOF OVERHANG COMPONENT AND CLADDING |
| PRESSURES ON A1 ARE NOT CORRECT. PLEASE CORRECT. SEE |
| FBC TABLE 1609.6.2.1(3). |
| |
| 8) PROVIDE A ROOF ZONE DIAGRAM FOR A GABLE ROOF ON A1. |
| SEE FBC FIGURE R301.2(8). |
| |
| 9) THE ENERGY CALCULATION FORM IS INCORRECT. WHEN USING |
| THE PRESCRIPTIVE METHOD C, THE INSULATION IS REQUIRED |
| TO BE THE MINIMUM SPECIFIED ON THE FORM. THEREFORE, THE |
| CONCRETE BLOCK IS REQUIRED TO HAVE R-5 INSULATION. SEE |
| FBC 13-600. |
| |
| 10) FBC 106.3* CITY AMENDMENTSPRODUCT APPROVALS. |
| THOSE PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 |
| SHALL BE REVIEWED AND APPROVED IN WRITING BY THE |
| DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| JURISDICTIONAL APPROVAL. |
| |
| 11) THE NOA FOR THE TRACO WINDOWS HAS BEEN REVISED BY |
| NOA NO. 05-0930.03. |
| |
| NOTE: IN ORDER TO EXPEDITE PLAN REVIEW PLEASE SUBMIT |
| ONE SET OF THE OLD DRAWINGS ALONG WITH THE NEW ONES. |
| ALSO SUBMIT BOTH OF THE DRAWINGS THAT HAVE THE COUNTY |
| IMPACT FEE STAMP OR THE NEW PLANS WILL HAVE TO BE |
| STAMPED BY THE COUNTY. |
| |
| ROBERT MCDOUGAL |
| BLDG. PLAN REVIEW |
| (561)805-6714 |
| [email protected] |
| |
| |
| |
| |