Plan Review Notes
Plan Review Notes For Permit 07110443
Permit Number 07110443
Review Stop E
Sequence Number 5
Notes
Date Text
2008-07-28 12:22:31 
  
 REVISION DENIED
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC CHAPTER 1 AS AMENDED AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING:
  
 1} PANEL "C" DOES NOT HAVE THE REQUIRED CLEARANCE PER
 110.26.
  
 2} THE #3 CU GROUNDING ELECTRODE IS IN VIOLATION OF
 250.66. A 1/0 IS REQUIRED FOR THE 400 AMP SERVICE AS IS
 ON THE PERMITTED SRT OF PLANS.
  
 3} THE RISER DIAGRAM INDICATES 2-#3 FEEDERS TO PANEL
 "D", THE PANEL SCHEDULE INDICATES #6 FEEDERS, CORRELATE
 SAME.
  
 4}SHOW COMPLIANCE WITH THE REQUIRED DISCONNECT PER
 440.14, FOR THE A/C COMPRESSERS.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718