Plan Review Notes For Permit 07110443 |
Permit Number |
07110443 |
|
Review Stop |
E |
Sequence Number |
5 |
|
Notes |
Date |
Text |
2008-07-28 12:22:31 | | | | | REVISION DENIED | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE | | CYCLES: | | | | THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004 | | RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002, | | NFPA-101 2003, 2004 FBC CHAPTER 1 AS AMENDED AND FOUND | | NONCOMPLIANT WITH THE FOLLOWING: | | | | 1} PANEL "C" DOES NOT HAVE THE REQUIRED CLEARANCE PER | | 110.26. | | | | 2} THE #3 CU GROUNDING ELECTRODE IS IN VIOLATION OF | | 250.66. A 1/0 IS REQUIRED FOR THE 400 AMP SERVICE AS IS | | ON THE PERMITTED SRT OF PLANS. | | | | 3} THE RISER DIAGRAM INDICATES 2-#3 FEEDERS TO PANEL | | "D", THE PANEL SCHEDULE INDICATES #6 FEEDERS, CORRELATE | | SAME. | | | | 4}SHOW COMPLIANCE WITH THE REQUIRED DISCONNECT PER | | 440.14, FOR THE A/C COMPRESSERS. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLANS EXAMINER | | CITY OF WEST PALM BEACH | | 561/805-6718 |
|