Plan Review Notes For Permit 07110443 |
Permit Number |
07110443 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2007-11-20 10:21:37 | | | | | | | | | | | PROVISO | | | | THERE ARE TWO SERVICE LOCATIONS INDICATED ON THE PLANS, | | REMOVE ONE. | | | | THE KITCHEN ISLAND MUST HAVE A RECEPTACLE TO COMPLY | | WITH 210.52(C)(2). | | | | BEDROOM #2 MUST HAVE ANOTHER RECEPTACLE ADDED TO COMPLY | | WITH 210.52(A)(1). | | | | THESE ITEMS MUST BE CORRECTED ON THE PLAN PRIOR TO | | SUBMITTING THE FIRST REVISION OR CALLING FOR ELECTRICAL | | INSPECTION. | | | | THE ARCHITECT MUST BE MADE AWARE OF THIS PROVISO. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLANS EXAMINER | | CITY OF WEST PALM BEACH | | 561/805-6718 | | [email protected] |
|