Plan Review Notes For Permit 07110417 |
Permit Number |
07110417 |
|
Review Stop |
B |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2008-01-22 15:49:55 | 2004 FBC W/2007 REVISIONS | | RESIDENTIAL REHAB | | | | DENIED BY BUILDING | | | | 1) A RECORDED COPY OF THE NOTICE OF | | COMMENCEMENT MUST BE SUBMITTED BEFORE A | | PERMIT CAN BE ISSUED. | | | | 2) THE INSTALLATION SCHEDULE FOR THE STORM PANELS IS | | INCORRECT. THE PLANS SHOW THE OPENING WIDTH FOR THE | | THREE FRONT WINDOWS THAT ARE MULLED TOGETHER AS 10'-2" | | (122") AND THE SCHEDULE THE WAS SUBMITTED HAS 101". | | THE SCHEDULE INDICATES THAT THE PANELS WILL ALL BE | | INSTALLED HORIZONTALLY. HOWEVER, TABLE 1 ON PAGE 9 OF | | THE PRODUCT APPROVAL ALLOWS A MAXIMUM SPAN OF 105" FOR | | 60 PSF. THE PRODUCT APPROVAL HAS BEEN MARKED TO | | INDICATE THAT A "H" HEADER WILL BE USED. HOWEVER, THIS | | CAN NOT BE USED IF THE PANELS ARE MOUNTED HORIZONTALLY. | | IF THE PANELS ARE MOUNTED VERTICALLY SPECIFY HOW THE | | BOTTOM WILL BE ATTACHED. | | | | 3) ONE SET OF PLANS DOES NOT HAVE THE EMBOSSED RAISED | | SEAL OF THE ENGINEER AS REQUIRED BY FS 471 AND FAC | | 61G-15-23.002. | | | | - ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|