2008-01-22 15:49:552004 FBC W/2007 REVISIONS
 RESIDENTIAL REHAB
  
 DENIED BY BUILDING
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) THE INSTALLATION SCHEDULE FOR THE STORM PANELS IS
 INCORRECT. THE PLANS SHOW THE OPENING WIDTH FOR THE
 THREE FRONT WINDOWS THAT ARE MULLED TOGETHER AS 10'-2"
 (122") AND THE SCHEDULE THE WAS SUBMITTED HAS 101".
 THE SCHEDULE INDICATES THAT THE PANELS WILL ALL BE
 INSTALLED HORIZONTALLY. HOWEVER, TABLE 1 ON PAGE 9 OF
 THE PRODUCT APPROVAL ALLOWS A MAXIMUM SPAN OF 105" FOR
 60 PSF. THE PRODUCT APPROVAL HAS BEEN MARKED TO
 INDICATE THAT A "H" HEADER WILL BE USED. HOWEVER, THIS
 CAN NOT BE USED IF THE PANELS ARE MOUNTED HORIZONTALLY.
 IF THE PANELS ARE MOUNTED VERTICALLY SPECIFY HOW THE
 BOTTOM WILL BE ATTACHED.
  
 3) ONE SET OF PLANS DOES NOT HAVE THE EMBOSSED RAISED
 SEAL OF THE ENGINEER AS REQUIRED BY FS 471 AND FAC
 61G-15-23.002.
  