2007-11-28 12:26:40 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & |
| REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM |
| BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA |
| ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES |
| (F.S.). |
| |
| *** DENIED *** |
| 1) THE MECHANICAL PLAN NEEDS TO SHOW THE SIZE OF THE |
| RETURN AIR TRANSFER DUCTS (FLEX) TO THE BEDROOMS, SEE |
| 2004 FBC/R M1602.4. |
| |
| 2) SHOW ON MECHANICAL PLAN HOW THE AIR IS RETURNING |
| BACK TO THE AIR HANDLER, SEE 2004 FBC/R M1602.1. |
| |
| 3) MECHANICAL PLANS SHOWS THE AIR HANDLES SUPPLYING |
| 1,032 CFM'S TO THE HOUSE, WHEN THE UNIT ONLY SUPPLIES |
| 800 CFM'S. PLEASE SUBMIT MANUAL D CALCULATIONS FOR |
| RESIDENTIAL DUCT DESIGN, PER 2004 FBC/R M1601.1 AND FBC |
| 13-610.1.ABC.1. DUCT SYSTEMS SERVING HEATING, COOLING |
| AND VENTILATION EQUIPMENT SHALL BE FABRICATED IN |
| ACCORDANCE WITH THE PROVISIONS OF THIS SECTION AND ACCA |
| MANUAL D OR OTHER APPROVED METHODS. (AND)ALL AIR |
| DISTRIBUTION SYSTEMS SHALL BE SIZED AND DESIGNED IN |
| ACCORDANCE WITH RECOGNIZED ENGINEERING STANDARDS SUCH |
| AS ACCA MANUAL D OR OTHER STANDARDS BASED ON THE |
| FOLLOWING: |
| |
| 4) ADD THE A/C EQUIPMENT LISTING WITH ALL PERTINENT |
| INFORMATION TO THE MECHANICAL PLAN NOT A SEPARATE |
| PAPER, SEE 2004 WPB AMEND. 106.3.5.4 (10). |
| |
| 5) SHOW THE LOCATION OF THE A/C CONDENSER UNIT ON THE |
| MECHANICAL PLAN. |
| |