Plan Review Notes
Plan Review Notes For Permit 07110417
Permit Number 07110417
Review Stop M
Sequence Number 1
Notes
Date Text
2007-11-28 12:26:40PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) THE MECHANICAL PLAN NEEDS TO SHOW THE SIZE OF THE
 RETURN AIR TRANSFER DUCTS (FLEX) TO THE BEDROOMS, SEE
 2004 FBC/R M1602.4.
  
 2) SHOW ON MECHANICAL PLAN HOW THE AIR IS RETURNING
 BACK TO THE AIR HANDLER, SEE 2004 FBC/R M1602.1.
  
 3) MECHANICAL PLANS SHOWS THE AIR HANDLES SUPPLYING
 1,032 CFM'S TO THE HOUSE, WHEN THE UNIT ONLY SUPPLIES
 800 CFM'S. PLEASE SUBMIT MANUAL D CALCULATIONS FOR
 RESIDENTIAL DUCT DESIGN, PER 2004 FBC/R M1601.1 AND FBC
 13-610.1.ABC.1. DUCT SYSTEMS SERVING HEATING, COOLING
 AND VENTILATION EQUIPMENT SHALL BE FABRICATED IN
 ACCORDANCE WITH THE PROVISIONS OF THIS SECTION AND ACCA
 MANUAL D OR OTHER APPROVED METHODS. (AND)ALL AIR
 DISTRIBUTION SYSTEMS SHALL BE SIZED AND DESIGNED IN
 ACCORDANCE WITH RECOGNIZED ENGINEERING STANDARDS SUCH
 AS ACCA MANUAL D OR OTHER STANDARDS BASED ON THE
 FOLLOWING:
  
 4) ADD THE A/C EQUIPMENT LISTING WITH ALL PERTINENT
 INFORMATION TO THE MECHANICAL PLAN NOT A SEPARATE
 PAPER, SEE 2004 WPB AMEND. 106.3.5.4 (10).
  
 5) SHOW THE LOCATION OF THE A/C CONDENSER UNIT ON THE
 MECHANICAL PLAN.
  
 MECHANICAL PLAN REVIEW BY;