Plan Review Notes For Permit 07110417 |
Permit Number |
07110417 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2007-11-19 10:34:40 | | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: | | | | THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004 | | RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002, | | NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND | | NONCOMPLIANT WITH THE FOLLOWING: | | | | ALL COMMENTS RELATE TO SHEET A1, UNLESS OTHERWISE | | NOTED. ALL CODE ARTICLES REFERENCED ARE 2005 NEC UNLESS | | OTHERWISE NOTED. | | | | 1} INDICATE IF THE ELECTRICAL SERVICE SHOWN ON THE PLAN | | IS NEW OR EXISTING. IF NEW INCLUDE IN THE DESCRIPTION | | ON THE APPLICATION, PROVIDE AN AIC RATING, AND LOCATE | | ALL SERVICE EQUIPMENT ON THE PLAN, METER ENCLOSURE, | | DISCONNECTS AND PANELS, SO THAT COMPLIANCE WITH | | ARTICLES 225 AND 230 CAN BE REVIEWED. PROVIDE A RISER | | DIAGRAM WITH CONDUCTOR AND CONDUIT SIZE AND TYPE. | | | | 2} DUE TO THE PANEL LOCATION, A DISCONNECT MAY BE | | REQUIRED PER 230.70, 225.32. INDICATE LOCATION ON PLAN | | PER 230.72(A)(1) . | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW. | | CITY OF WEST PALM BEACH | | 561/805-6718 | | [email protected] |
|