Notes
Date Text
2007-11-19 14:28:072004 FBC W/2007 REVISIONS
 RESIDENTIAL REHAB
  
 DENIED BY BUILDING
  
 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT
 MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) THE SCOPE OF WORK ON A1 SPECIFIES THAT A 2'-8" STEEL
 DOOR IS TO BE INSTALLED. THE PLANS SHOW A 2'-8" INSWING
 EXTERIOR DOOR AND THE PRODUCT APPROVAL THAT WAS
 SUBMITTED IS FOR AN OUTSWING DOOR. PLEASE CLARIFY.FBC
 *106.1.1 CITY AMENDMENTS
  
 3)SPECIFY THE COMPONENT AND CLADDING PRESSURES FOR
 THE EXTERIOR DOOR THAT IS BEING REPLACED. SEE FBC TABLE
 R301.2(2).
  
 4) SUBMIT A KEY PLAN AND INSTALLATION SCHEDULE FOR THE
 STORM PANELS. SPECIFY THE MOUNT TYPE, ANCHOR TYPE AND
 SPACING, SPAN, EDGE DISTANCE, ETC. THIS INFORMATION IS
 CONTAINED IN THE PRODUCT APPROVAL. SEE ATTACHED SAMPLE
 INSTALLATION SCHEDULE.
  
 5) SUBMIT ENERGY CALCULATIONS ON FORM 600C-04R AS
 REQUIRED BY FBC 13-101.4.1.
  
 - ROBERT MCDOUGAL
 BLDG. PLAN REVIEW