Plan Review Notes For Permit 07110407 |
Permit Number |
07110407 |
|
Review Stop |
FIRE |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2008-05-08 14:12:52 | ***DENIED*** | | | | 1) IT APPEARS THAT REQUIRED CLEARANCE AROUND THE | | ELECTRICAL PANEL MAY BE COMPROMISED. ACCESS TO | | ELECTRICAL SERVICE SHALL BE PROVIDED. NFPA 101, SEC. | | 9.1.2 | | | | 2) IF AN EMERGENCY SHOULD OCCUR IN THE AREA SERVED BY | | THE ELECTRICAL SERVICE, HOW WILL EMERGENCY PERSONNEL | | DETERMINE THE LOCATION OF THE SERVICE AND ACCESS THE | | PANEL? | | | | | | MIKE WENNERGREN, ASSISTANT FIRE MARSHAL | | FIRE PLAN REVIEW | | FIRE PREVENTION (561) 804-4756 |
|