2008-04-11 17:27:57BUILDING PLAN REVIEW
 PERMIT: 07110407
 ADD: 1411 N. FLAGLER DR 8900B
 CONT: ANDERSON MOORE CONST.
 TEL: (561)753-7400
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 4-11-08
 REVIEW: REVISION
 ACTION: DENIED
  
 1)THE ORIGINAL PLANS SHOWS WALL P-3 BEHIND THE
 ELECTRICAL PANELS ON SHEET A.1. THE REVISION NOW SHOWS
 THE SAME WALL IN FRONT OF THE ELECTRICAL PANELS WHICH
 WILL MAKE THE PANELS INACCESSIBLE. IT SEEMS AS THOUGH A
 NEW ELECTRICAL CLOSET IS BEING CREATED BY ADDING THESE
 DOORS WHICH MAY BE AN ELECTRICAL VIOLATION. THE
 ELECTRICAL PAGES SHALL BE REVISED TO SHOW THE LOCATION
 OF THE DOORS IN RELATION TO THE PANELS FOR THE REQUIRED
 CLEARANCE FOR ELECTRICAL CLOSETS. THE ONLY CODE SECTION
 IN THE BUILDING CODE WHICH COVERS THIS SITUATION IS FBC
 2701.1 SCOPE.
 THIS CHAPTER GOVERNS THE ELECTRICAL COMPONENTS,
 EQUIPMENT AND SYSTEMS USED IN BUILDINGS AND STRUCTURES
 COVERED BY THIS CODE. ELECTRICAL COMPONENTS, EQUIPMENT
 AND SYSTEMS SHALL BE DESIGNED AND CONSTRUCTED IN
 ACCORDANCE WITH THE PROVISIONS OF THE NFPA 70, NATIONAL
 ELECTRICAL CODE, EXCEPT ARTICLE 80.
 THE ELECTRICAL PLAN REVIEWER WILL HAVE TO REVIEW THIS
 CHANGE BEFORE THE DOORS ARE APPROVED. ADDITIONAL
 INFORMATION IS REQUIRED WPB AMENDMENTS 106.1.2
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]