2007-12-10 18:13:05 | ****CORRECTIONS**** | | ****REVISION FOR SECONDARY WATER BARRIER*** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | | | FBCFLORIDA BUILDING CODE 2004 | | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING | | CODE | | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC* | | CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | | | FAC FLORIDA ADMINISTRATIVE CODE | | FSFLORIDA STATUTE | | | | 1.THE UNDERLAYMENT YOU REFER TO IN THE LETTER, TU | | PLUS, IS A TILE UNDERLAYMENT.IR/IRX IS THE | | MANUFACTURER'S RECOMMENDED SHINGLE UNDERLAYMENT. | | PROVIDE DOCUMENTATION FROM THE MANUFACTURER WHICH SHOWS | | THAT TU PLUS IS AN ACCEPTABLE SHINGLE UNDERLAYMENT. | | | | 2.PLEASE PRINT THE SUPPORTING DOCUMENTATION FOR THE | | UNDERLAYMENT.THIS SHOULD INCLUDE THE EVALUATION | | REPORT AND INSTALLATION INSTRUCTIONS AND ARE LINKS FROM | | THE FLORIDA STATE PRODUCT APPROVAL WEB PAGE.THE NOA | | SUBMITTED WITH THE ORIGINAL PERMIT DOES NOT ALLOW | | DIRECT DECK APPLICATION. | | | | 3.WHEN RESUBMITTING, THIS IS CONSIDERED "ENGINEERING" | | AND DOES NOT REQUIRE AN ADDITIONAL HISTORIC REVIEW. | | YOU MAY PROVIDE THIS CORRECTION LIST AT THE FRONT DESK | | COUNTER WHEN RESUBMITTING. | | | | | | |
|