2007-11-14 16:46:19 | ****CORRECTIONS**** |
| SAMANTHA HILL, BUILDING PLANS EXAMINER |
| 561-805-6724 [email protected] |
| |
| FBCFLORIDA BUILDING CODE 2004 |
| FBC EBFLORIDA BUILDING CODE 2004 |
| EXISTING BUILDING CODE |
| FBC*CITY OF WEST PALM BEACH |
| AMENDMENTS TO THE FBC2004 |
| |
| 1.)EFFECTIVE OCTOBER 1, 2007, SECONDARY WATER BARRIER |
| REQUIRED FS553.844(5)(A). PROVIDE INFORMATION |
| (PRODUCT APPROVAL OR SPECIFICATIONS) TO SHOW HOW YOU |
| WILL COMPLY WITH THIS REQUIREMENT.INFORMATION MAY BE |
| AVAILABLE AT WWW.BOAF.NET, HURRICANE MITIGATION. |
| |
| PER CONVERSATION WITH CONTRACTOR, 4" TAPE AT THE SEAMS |
| WILL BE USED FOR THE SHINGLE PITCHED ROOF.PROVIDE |
| SPEC SHEET OR PRODUCT APPROVAL. |
| |
| PER CONVERSATION WITH CONTRACTOR, ONE ADDITIONAL PLY |
| SHEET WILL BE INSTALLED (TWO PLY SHEETS) TO COMPLY WITH |
| THE SECONDARY WATER BARRIER REQUIREMENT FOR THE LOW |
| SLOPE ROOF.TO SHOW CODE COMPLIANCE AND TO AVOID |
| MISUNDERSTANDING/DELAYS IN INSPECTIONS IN THE FIELD, |
| PLEASE SUMMARIZE EACH SYSTEM WITH A DETAILED |
| DESCRIPTION (DESCRIPTION OF LAYERS, NOT FASTENING). |
| |
| THE TILE ROOF FALLS UNDER THE EXCEPTION FS553.844; NO |
| ADDITIONAL WATER BARRIER REQUIRED. |
| |
| 2.)AS YOU HAVE THREE DIFFERENT ROOF SYSTEMS, PLEASE |
| PROVIDE A ROOF PLAN. |
| |
| 3.)PROVIDE INFORMATION IN REGARDS TO THE ROOF TILE |
| INSTALLATION AREA.IF A TILE ROOF IS NOT CURRENTLY |
| INSTALLED, ENGINEERING ADDRESSING THE ADDITIONAL DEAD |
| LOAD WILL BE REQUIRED. |
| |
| 4.)ON THE TILE PRODUCT APPROVAL, INDICATE WHICH |
| METHOD OF ATTACHMENT YOU ARE USING.IF YOU SELECT FOAM |
| ADHESIVE, PRODUCT APPROVALS REQUIRED FAC9B72. |