2007-11-27 15:02:28PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) ELEVATOR PLAN PAGE 4 OF 4 STATES "VENTILATED
 TEMPERATURE CONTROLLED MACHINE ROOM". PLANS DO NOT
 STATE WITH WHAT THE ROOM IS TO BE VENTILATED AND
 TEMPERATURE CONTROLLED. PLEASE SHOW ON PLAN IF THIS IS
 DONE BY AN A/C SYSTEM OR HOW,SHOW ALL DETAIL AND
 PROVIDE ALL INFORMATION. SEE 2004 FBC 3006.2.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]