2007-11-26 14:34:19 
  
 APPLICATION #07110294
 ELECTRICAL PLAN REVIEW
 927 BELVEDERE ROAD
 11/26/07
 WEST PALM BEACH, FL.
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1, AND
 FOUND NONCOMPLIANT WITH THE FOLLOWING:
 ARTICLES REFERENCED ARE 2005 NEC UNLESS OTHERWISE
 NOTED.
  
 1} INDICATE PANEL DESIGNATION AND CIRCUIT NUMBERS FOR
 LIGHTS AND RECEPTACLES REQUIRED BY 620.23.
  
 2} INDICATE COMPLIANCE WITH 620.85, GROUND-FAULT
 CIRCUIT-INTERRUPTER PROTECTION FOR PERSONNEL.
  
 3} INDICATE THE LOCATION AND FEEDER DESIGNATION (PANEL
 AND CIRCUIT) FOR THE DISCONNECTING MEANS REQUIRED PER
 620.51. THE ELEVATOR DRAWINGS INDICATE A PIT, THE
 ARCHITECTURAL DRAWINGS SEEM TO INDICATE MACHINE ROOM,
 PLEASE CORRELATE.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER