Plan Review Notes
Plan Review Notes For Permit 07110294
Permit Number 07110294
Review Stop B
Sequence Number 1
Notes
Date Text
2007-11-21 14:00:34 
 BUILDING PLAN REVIEW
 PERMIT: 07110294
 ADD: 927 BELVEDERE RD
 CONT: H. CHNO CONSTRUCTION
 TEL: (561)856-6655
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 1ST
 ACTION: DENIED
  
 1A)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 1B) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT
 ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 2)606.1 GENERAL.
 A BUILDING, FACILITY, OR ELEMENT THAT IS ALTERED SHALL
 COMPLY WITH CHAPTER 11 OF THE FLORIDA BUILDING CODE,
 BUILDING.
  
 3)NOW AN ELEVATOR IS PROPOSED TO BE INSTALLED, THE
 BUILDING WILL BE REQUIRED TO HAVE AN AREA IF RESCUE
 ASSISTANCE MEETING THE REQUIREMENTS OF FBC SECTION
 11-4.3.11.
  
 4) THE ENTIRE SECOND FLOOR PLAN IS REQUIRED TO SHOW ALL
 MEANS OF EGRESS IN THE BUILDING.
  
 5)INDICATE ON THE PLANS IF THE BUILDING HAS A
 SPRINKLER SYSTEM. AN AUTOMATIC SPRINKLER SYSTEM SHALL
 BE PROVIDED FOR GROUP A-3 OCCUPANCY, WHERE THE OCCUPANT
 LOAD IS 300 OR MORE AND THE FLOOR IS LOCATED ON A FLOOR
 OTHER THAN THE LEVEL OF EXIT DISCHARGE. FBC 903.2.1.3.
 BUILDINGS AND OTHER STRUCTURES WHERE MORE THAN 300
 PEOPLE CONGREGATE IN ONE AREA ARE CATEGORY III WITH AN
 IMPORTANCE FACTOR OF 1.15 PER TABLE 1604.5
  
 6)IF THE ELEVATION OF THE BUILDING ON SHEET A-2 IS
 32?-6?, HOW CAN THE MEAN ROOF HEIGHT BE 13? ON SHEET
 A-1? NOTE: THE ASCE 7-98 IS IN THE 2001 CODE, THE FBC
 2004 REFERS TOASCE 7-02. SEE FBC CHAPTER 35 FOR MORE
 INFORMATION.
  
 7)THE PRODUCT APPROVAL SUBMITTED SHALL BE APPROVED IN
 WRITING BY THE DESIGNER OF RECORD. CIRCLE OR HI-LIGHT
 ALL ITEMS TO BE USED FOR THE INSTALLATION OF THE NEW
 EXTERIOR DOOR 106.3.3*
  
 8)PROVIDE A DETAIL ELEVATION DRAWING OF THE NEW
 OPENING LEADING TO THE ASSEMBLY AREA ON THE SECOND
 FLOOR.
  
 9) THE MACHINE ROOM SHALL MEET THE REQUIREMENTS OF FBC
 3006.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]
  
  
  