Plan Review Notes For Permit 07110276 |
Permit Number |
07110276 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2007-11-09 16:58:31 | ****CORRECTIONS**** | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | | | FBCFLORIDA BUILDING CODE 2004 | | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING | | CODE | | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL | | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | | | FAC FLORIDA ADMINISTRATIVE CODE | | FSFLORIDA STATUTE | | | | 1.)PRODUCT APPROVALS ARE TO BE APPROVED BY DESIGNER | | OF RECORD (SHOP DRAWING REVIEW STAMP OR LETTER), | | FBC*106.3.3. | | | | 2.)FOR THE FLAT DECK, SELECT THE APPROVED ASSEMBLY | | YOU ARE USING.ALSO INDICATE WHICH FASTENER YOU ARE | | USING IF THE OPTIONS HAVE DIFFERENT PRESSURE | | LIMITATIONS. | | | | 3.)SEE GENERAL LIMITATION #7 ON THE NOA. | | CALCULATIONS PREPARED BY AN ARCHITECT, ENGINEER, OR | | REGISTERED ROOF CONSULTANT REQUIRED FOR ENHANCED | | FASTENING. | | |
|