Plan Review Notes For Permit 07110227 |
Permit Number |
07110227 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2007-11-16 09:46:45 | ****CORRECTIONS**** | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | | | FBCFLORIDA BUILDING CODE 2004 | | FBC EBFLORIDA BUILDING CODE 2004 | | EXISTING BUILDING CODE | | FBC*CITY OF WEST PALM BEACH | | AMENDMENTS TO THE FBC2004 | | | | 1.THE SYSTEM SUBMITTED DOES NOT COMPLY WITH THE | | SECONDARY WATER BARRIER REQUIREMENTS.PLEASE SEE | | WWW.BOAF.NET, HURRICANE MITIGATION.IF YOU ARE USING | | AN ADDITIONAL PLY WITHIN THE MODIFIED SYSTEM TO COMPLY | | WITH THE SECONDARY WATER BARRIER REQUIREMENT, IT MUST | | BE AN APPROVED CAP SHEET.THE OPTIONAL PLY SHEET YOU | | HAVE SPECIFIED, GAFGLAS 4, IS NOT AN APPROVED CAP SHEET | | (PLY SHEET ONLY).SEE SHEET 28 OF THE NOA. | | | | |
|