Plan Review Notes For Permit 07110162 |
Permit Number |
07110162 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2007-11-08 08:07:45 | 2004 FBC | | ROOF FOR COVERED WALKWAY | | | | DENIED BY BUILDING | | | | ALTHOUGH THE INFORMATION SUBMITTED FOR THE ROOF SYSTEM | | IS CODE COMPLIANT FOR INSTALLATION OVER A WOOD DECK, | | THE APPROVED PLANS FOR THE COVERED WALK WAY ( SECTIONS | | 4 AND 5 ON A1.2.4 AND S13) DO NOT SPECIFY A WOOD DECK | | WITH A MODIFIED BITUMEN ROOF SYSTEM. THE PLANS FOR THE | | MASTER PERMIT ( # 05121217) WILL NEED TO BE REVISED. | | THE PERMIT FOR THE ROOF COVERING CAN NOT BE ISSUED | | UNTIL THE REVISION HAS BEEN APPROVED. | | | | -ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|