2008-01-08 09:23:13 | *** PROVISO *** | | 1) AIR HANDLER #2 NEEDS TO COMPLY WITH 2004 FBC/R | | M1305.1.2 APPLIANCES IN ROOMS. | | APPLIANCES INSTALLED IN A COMPARTMENT, ALCOVE, BASEMENT | | OR SIMILAR SPACE SHALL BE ACCESSED BY AN OPENING OR | | DOOR AND AN UNOBSTRUCTED PASSAGEWAY MEASURING NOT LESS | | THAN 24 INCHES WIDE AND LARGE ENOUGH TO ALLOW REMOVAL | | OF THE LARGEST APPLIANCE IN THE SPACE, PROVIDED THAT A | | LEVEL SERVICE SPACE OF NOT LESS THAN 30 INCHES DEEP AND | | THE HEIGHT OF THE APPLIANCE, BUT NOT LESS THAN 30 | | INCHES, IS PRESENT AT THE FRONT OR SERVICE SIDE OF THE | | APPLIANCE WITH THE DOOR OPEN. | | | | 2) RETURN AIR NEEDS TO BE PROVIDED FOR TO THE SITTING | | ROOM AND BEDROOMS, SO THAT IT MAY RETURN TO THE AIR | | HANDLER IN COMPLIANCE WITH 2004 FBC/R M1602.4. | | | | MECHANICAL PLAN REVIEW BY; | | TOM GORDON (561) 805-6729 | | E-MAIL; [email protected] |
|