Plan Review Notes
Plan Review Notes For Permit 07110158
Permit Number 07110158
Review Stop M
Sequence Number 1
Notes
Date Text
2007-11-26 12:17:41PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) NEED TO SUBMIT THE COMPLETE ENERGY CALCULATIONS, NOT
 JUST TWO PAGES, SEE 4004 FBC 13-600.3.A.
  
 2) ENERGY CALCULATIONS NEED TO BE SIGNED BY THE
 PREPARER AND THE OWNER/AGENT, PER 2004 FBC
 13-600.3.ABC.2.
  
 3) NEED TO SUBMIT TWO (2) COPIES OF THE ENERGY
 CALCULATIONS AND THE COOLING LOAD CALCULATIONS, SEE
 2004 WPB AMEND. 106.1.
  
 4) PLEASE ADD AN A/C EQUIPMENT SCHEDULE TO THE
 MECHANICAL PLAN SHOWING ALL PERTINENT INFORMATION, SEE
 2004 WPB AMEND. 106.3.5.4 (10).
  
 5) THE MECHANICAL PLAN SHOWS ACCESS TO AIR HANDLER #2
 AT THE WATER CLOSET, PER 2004 FBC/R M1305.1 THIRTY
 INCHES OF WORKING SPACE SHALL BE PROVIDED IN FRONT OF
 THE CONTROL SIDE TO SERVICE AN APPLIANCE. PLEASE
 CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]