Plan Review Notes For Permit 07110158 |
Permit Number |
07110158 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2007-11-26 12:17:41 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & | | REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST | | PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA | | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES | | (F.S.). | | | | *** DENIED *** | | 1) NEED TO SUBMIT THE COMPLETE ENERGY CALCULATIONS, NOT | | JUST TWO PAGES, SEE 4004 FBC 13-600.3.A. | | | | 2) ENERGY CALCULATIONS NEED TO BE SIGNED BY THE | | PREPARER AND THE OWNER/AGENT, PER 2004 FBC | | 13-600.3.ABC.2. | | | | 3) NEED TO SUBMIT TWO (2) COPIES OF THE ENERGY | | CALCULATIONS AND THE COOLING LOAD CALCULATIONS, SEE | | 2004 WPB AMEND. 106.1. | | | | 4) PLEASE ADD AN A/C EQUIPMENT SCHEDULE TO THE | | MECHANICAL PLAN SHOWING ALL PERTINENT INFORMATION, SEE | | 2004 WPB AMEND. 106.3.5.4 (10). | | | | 5) THE MECHANICAL PLAN SHOWS ACCESS TO AIR HANDLER #2 | | AT THE WATER CLOSET, PER 2004 FBC/R M1305.1 THIRTY | | INCHES OF WORKING SPACE SHALL BE PROVIDED IN FRONT OF | | THE CONTROL SIDE TO SERVICE AN APPLIANCE. PLEASE | | CORRECT. | | | | MECHANICAL PLAN REVIEW BY; | | TOM GORDON (561) 805-6729 | | E-MAIL; [email protected] |
|