 APPLICATION #07110158
 3212 ALTON ROAD
 ELECTRICAL PLAN REVIEW
 WEST PALM BEACH, FL
 11/16/07
 .
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1, AND
 FOUND NONCOMPLIANT WITH THE FOLLOWING:
 ARTICLES REFERENCED ARE 2005 NEC UNLESS OTHERWISE
 NOTED.
  
 1} THERE ARE TWO SHEETS NUMBERED 10.1., RENUMBER ONE TO
 MATCH THE SEQUENCE 106.1.3 FBC.
  
 2} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST
 PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.3. FBC.
 IF AN ARCHITECT OR ENGINEER, COMPLY WITH 481 AND 471
 FS, RESPECTIVELY. THE CONTRACTOR OF RECORD MAY BE THE
 DESIGN PROFESSIONAL IF EXEMPTIONS UNDER CHAPTER
 471.003, FLORIDA STATUTES, IF EXEMPTIONS APPLY.
  
 3} SMOKE ALARMS MUST BE INSTALLED TO COMPLY WITH R313.1
 RESIDENTIAL FLORIDA BUILDING CODE. ALSO 210.12 DICTATES
 THEY BE ON AN ARC FAULT CIRCUIT. THE SMOKE DETECTOR
 CIRCUITS LISTED ON THE PLAN ARE 1) NOT ARC FAULT AND 2)
 ON MULTIPLE CIRCUITS, WHICH WOULD PROHIBIT THE REQUIRED
 INTERCONNECTION.
  
 4} THE DINING ROOM CIRCUITS ARE MISMARKED AS 5 IN THE
 PANEL AND 7 AT THE RECEPTACLES.
  
 5} DUE TO THE METER LOCATION, AND THE PANEL LISTED AS
 MLO, A DISCONNECT IS REQUIRED PER 230.70, 225.32.
 INDICATE LOCATION ON PLAN AND ADD TO THE RISER DIAGRAM,
 PER 230.72(A)(1)
 .
 6} THE AIC RATING IS LISTED AS 22000 ON THE RISER AND
 10000 IN THE PANEL. CORRELATE SAME.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  