Plan Review Notes
Plan Review Notes For Permit 07110158
Permit Number 07110158
Review Stop B
Sequence Number 1
Notes
Date Text
2007-11-21 11:17:422004 FBC W/2007 REVISIONS
 ADDITION AND LEVEL 2 ALTERATION
  
 DENIED BY BUILDING
  
 1) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2) " WHITE-OUT" ONPLANS IS NOT ACCEPTABLE. SEE FBC*
 106.1.3 CITY AMENDMENTS AND FS 471.
  
 3) THE PERMIT APPLICATION INDICATES THAT THIS PROJECT
 IS TO BE DONE IN PHASES. THE FIRST FLOOR ADDITION BEING
 PHASE ONE AND A SECOND STORY TO BE PHASE TWO. THE PLANS
 WILL NEED TO BE RE-DRAWN SHOWING ONLY THE FIRST FLOOR
 WITH THE ROOF ABOVE IT. THE ELEVATIONS AND OTHER
 DRAWINGS SHOULD SHOW THE ONE STORY STRUCTURE WITH NOTES
 INDICATING FUTURE SECOND STORY. SEE FBC* 106.1.1 CITY
 AMENDMENTS.
  
 4) THE DESIGN PARAMETERS ON SHEET 4.1 SPECIFIES THE
 WIND EXPOSURE CATEGORY AS C AND THE COMPONENT AND
 CLADDING TABLE PRESSURES ON SHEET 7 ARE FOR EXPOSURE B.
 PLEASE CORRECT. SEE FBC R301.2.1.4 AND TABLE
 R301.2(2).
  
 5) SPECIFY SAFETY GLAZING IN THE BATHROOM WINDOWS AS
 REQUIRED BY FBC R308.3.
  
 6) SPECIFY THE HEIGHT OF THE LOW PARAPET WALLS ON THE
 PLANS. FBC* 106.1.1 CITY AMENDMENTS
  
 7) ON SHEET 6.1, NUMBER 22 ON THE CONNECTOR SCHEDULE IS
 SPECIFIED AS A SIMPSON LUS 10. IS THIS SUPPOSE TO BE A
 LUS 210? PLEASE CLARIFY.
  
 8) THE SPACING FOR THE VERTICAL REINFORCING BARS FOR
 THE FIRST FLOOR ON SHEET 3.1 IS NOT ADEQUATE. PLEASE
 REVIEW AND CORRECT. SEE FBC R 609.3.
  
 9) SPECIFY THE LOCATIONS AND SIZE OF VERTICAL
 REINFORCING BARS FOR THE SECOND FLOOR WALLS AND THE
 PARAPET WALLS. SEE FBC* 106.1.1 CITY AMENDMENTS AND FBC
 R 609.3.
  
 10) SHOW COMPLIANCE WITH R806.1 VENTILATION REQUIRED.
 ENCLOSED ATTICS AND ENCLOSED RAFTER SPACES FORMED WHERE
 CEILINGS ARE APPLIED DIRECTLY TO THE UNDERSIDE OF ROOF
 RAFTERS SHALL HAVE CROSS VENTILATION FOR EACH SEPARATE
 SPACE BY VENTILATING OPENINGS PROTECTED AGAINST THE
 ENTRANCE OF RAIN. VENTILATING OPENINGS SHALL BE
 PROVIDED WITH CORROSION-RESISTANT WIRE MESH, WITH 1 / 8
 INCH (3.2 MM) MINIMUM TO 1/4 INCH (6.4 MM) MAXIMUM
 OPENINGS.
  
 11) THE ROOF SHEATHING NAILING AT THE BOTTOM OF THE
 CONNECTOR SCHEDULE ON SHEET 6.1 IS INCORRECT AND DOES
 NOT CORRESPOND TO FASTENING SPECIFIED ELSEWHERE ON THIS
 SHEET. SEE FBC R803.2.3.1.
  
 12) PROVIDE A DETAIL OF THE STEEL COLUMN SHOWN AT THE
 CORNER OF THE WINDOW OPENINGS AT THE SECOND FLOOR
 MASTER BEDROOM. SEE FBC* 106.1.1 CITY AMENDMENTS.
  
 13) ON SHEET 8.1 AN ELEVATION OF 20'-4" IS SPECIFIED AS
 THE T.O. BEAM AND IT APPEARS TO BE THE BOTTOM OF THE
 BEAM. PLEASE CLARIFY.
  
 14) SPECIFY THE LINTELS ABOVE THE SECOND FLOOR WINDOWS.
 SEE FBC* 106.1.1 CITY AMENDMENTS.
  
 15) PLEASE REMOVE THE EXTERIOR BEARING WALL DETAIL 5 ON
 8.2 WHICH DOES NOT APPLY TO THIS PROJECT.
  
 16) SECTION 1 ON 6.1 REFERS TO DETAIL #12 ON SHEET 6.2.
 HOWEVER, THERE WAS NO SHEET 6.2 SUBMITTED.
  
 17) SUBMIT TWO COPIES OF THE ENERGY CALCULATIONS THAT
 HAVE BEEN SIGNED AND DATED BY THE PREPARER AND
 OWNER/AGENT AS REQUIRED BY FBC CHAPTER 13.101.2.
  
 18) THE ENERGY CALC. FORM LISTS THE EXTERIOR CONCRETE
 WALL INSULATION AS R-5 AND SECTION 1 ON 8.1 SPECIFIES
 R-4.2 INSULATION. PLEASE CORRECT.
  
 19) THE CONDITIONED SPACE ON THE ENERGY CALC. FORM
 LISTS 2363 SQFT AND THE PLANS SPECIFY 2358 SQFT. PLEASE
 CORRECT.
  
 20)PRODUCT APPROVALS SUBMITTED WITH PERMIT
 APPLICATION AFTER OCTOBER 1, 2003 ARE REQUIRED TO
 COMPLY WITH THE FLORIDA PRODUCT APPROVAL SYSTEM. FOR
 INFORMATION PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH STATEWIDE
 APPROVAL ARE REQUIRED TO BE SUBMITTED WITH A COVER
 SHEET THAT LISTS THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. SEE FAC RULE 9B-72. SUBMIT PRODUCT APPROVALS FOR
 THE INSWING AND OUTSWING EXTERIOR DOORS, WINDOW
 MULLIONS AND ROOFING MATERIAL.
  
 21) FBC *106.3 CITY AMENDMENTS. PRODUCT APPROVALS.
 THOSE PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 22)FBC 1606.1.4SHUTTERS.
 INSTALLATION/DESIGN INFORMATION
 REQUIRED.SUBMIT AN INSTALLATION
 SCHEDULE INCLUDING THE FOLLOWING
 DETAILS:
 (A) BUILDING CONSTRUCTION TYPE (EG CBS)
 (B) BUILDING (OR INSTALLATION) HEIGHT
 (C) DESIGN PRESSURE FOR EACH OPENING
 (D) OPENING SIZES
 (E) SHUTTER SPAN (VERTICAL/HORIZONTAL?)
 (F) ANCHOR TYPE, SIZE AND SPACING
 A FORM IS AVAILABLE FROM THIS OFFICE
 GIVING THE RECOMMENDED INSTALLATION
 SCHEDULE FORMAT.SUBMIT THE ABOVE
 INFORMATION WHICH IS REQUIRED FOR
 REVIEW.
  
 23) SHOW COMPLIANCE WITH R310.4. THE TEMPORARY
 INSTALLATION OR CLOSURE OF STORM SHUTTERS, PANELS, AND
 OTHER APPROVED HURRICANE PROTECTION DEVICES SHALL BE
 PERMITTED ON EMERGENCY ESCAPE AND RESCUE OPENINGS
 DURING THE THREAT OF A STORM. SUCH DEVICES SHALL NOT BE
 REQUIRED TO COMPLY WITH THE OPERATIONAL CONSTRAINTS OF
 SECTION R310.1.4 . WHILE SUCH PROTECTION IS PROVIDED,
 AT LEAST ONE MEANS OF ESCAPE FROM THE DWELLING OR
 DWELLING UNIT SHALL BE PROVIDED. THE MEANS OF ESCAPE
 SHALL BE WITHIN THE FIRST FLOOR OF THE DWELLING OR
 DWELLING UNIT AND SHALL NOT BE LOCATED WITHIN A GARAGE
 WITHOUT A SIDE HINGED DOOR LEADING DIRECTLY TO THE
 EXTERIOR. OCCUPANTS IN ANY PART OF THE DWELLING OR
 DWELLING UNIT SHALL BE ABLE TO ACCESS THE MEANS OF
 ESCAPE WITHOUT PASSING THROUGH A LOCKABLE DOOR NOT
 UNDER THEIR CONTROL.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]