2007-11-20 07:14:41 | | | | | | | APPLICATION #07110124 | | ELECTRICAL PLAN REVIEW | | 2400 PRESIDENTIAL WAY #303 | | 11/20/07 | | WEST PALM BEACH, FL. | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: | | | | THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004 | | RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002, | | NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1, AND | | FOUND NONCOMPLIANT WITH THE FOLLOWING: | | ARTICLES REFERENCED ARE 2005 NEC UNLESS OTHERWISE | | NOTED. | | | | 1} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST | | PRINT AND SIGN THEIR NAME TO SAME, ALL SHEETS, PER | | 106.1.3.FBC. | | | | 2} PLEASE INCLUDE THE ADDRESS OF THE PROJECT ON ALL | | SHEETS OF THE PLANS FOR RECORD RETENTION.106.1.3.FBC AS | | AMENDED. | | | | 3} PER 2704.1, 2004 FBC, METAL FRAMING MEMBERS SHALL BE | | BONDED TO THE EQUIPMENT GROUNDING CONDUCTOR FOR THE | | CIRCUIT THAT MAY ENERGIZE THE FRAMING. PLEASE SEE | | ARTICLE. NOTE SAME ON PLANS. | | | | 4} DECLARE THE USE OF THE BUILDING PER CHAPTER 3, FBC. | | 301.5 | | A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE OR A | | COMBINATION OF LEVELS OF ALTERATION PURSUANT TO | | SECTIONS 303, 304 AND 305 OF THIS CODE. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLANS EXAMINER | | CITY OF WEST PALM BEACH | | 561/805-6718 | | [email protected] |
|