 APPLICATION #07110124
 ELECTRICAL PLAN REVIEW
 2400 PRESIDENTIAL WAY #303
 11/20/07
 WEST PALM BEACH, FL.
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1, AND
 FOUND NONCOMPLIANT WITH THE FOLLOWING:
 ARTICLES REFERENCED ARE 2005 NEC UNLESS OTHERWISE
 NOTED.
  
 1} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST
 PRINT AND SIGN THEIR NAME TO SAME, ALL SHEETS, PER
 106.1.3.FBC.
  
 2} PLEASE INCLUDE THE ADDRESS OF THE PROJECT ON ALL
 SHEETS OF THE PLANS FOR RECORD RETENTION.106.1.3.FBC AS
 AMENDED.
  
 3} PER 2704.1, 2004 FBC, METAL FRAMING MEMBERS SHALL BE
 BONDED TO THE EQUIPMENT GROUNDING CONDUCTOR FOR THE
 CIRCUIT THAT MAY ENERGIZE THE FRAMING. PLEASE SEE
 ARTICLE. NOTE SAME ON PLANS.
  
 4} DECLARE THE USE OF THE BUILDING PER CHAPTER 3, FBC.
 301.5
 A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE OR A
 COMBINATION OF LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 303, 304 AND 305 OF THIS CODE.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  