Plan Review Notes
Plan Review Notes For Permit 07110087
Permit Number 07110087
Review Stop ENG
Sequence Number 1
Notes
Date Text
2007-11-16 10:49:34FAILED FOR FOLLOWING REASONS:
  
 1. DUMPSTER LOCATION MUST BE ACCESSIBLE FOR PICKUP
 TRUCK.
 2. PLEASE SHOW ON CALCULATION THAT YOU HAVE CONSIDERED
 FLOOD ZONE AREA, & 5,10, 25, 100 YEAR FLOOD CRITERIA
 AND CROWN OF THE ROAD WHEN YOU DETERMINE THE FIRST
 FLOOR ELEVATION.
 3. PLEASEMAKE SURE THESE AREAS SHOWN ON DRAINAGE
 DRAWINGS MUST MATCH WITH AND USED IN STORM WATER
 QUALITY CALCULATIONS. PLEASE PROVIDE A COPY OF THESE
 CALCULATIONS.
 4. PLEASE SHOW ALL STORM WATER PIPES AROUND YOUR SITE
 SO, WE CANSEE THE LAYOUT OF STORM WATER PIPES FROM
 ALL OTHER STORM WATER PIPES. PLEASE SHOW DETAIL OF THE
 CONTROL STRUCTURESWITH ELEVATIONS, NOTCHES, BLEEDING
 ELEVATION, ETC ON DRAWINGS, CALCULATION FOR
 EXFILTRATION TRENCHES, PLEASE SHOW DRY DETENTION/WET
 DETENTION AREAS IN STORM WATER CALS IF YOU HAVE ALL
 THESE.
 5. ALSO PLEASE SHOW ALL CATCH BASINS NEAREST,AROUND
 YOUR SITE FOR STORM WATER DRAIN SO YOUR SITE DO NOT GET
 FLOODED AND HAVE ENOUGH DRAINS.
 6. PLEASE PROVIDE A COPY OF SFWMD PERMIT,, &STORM
 WATER QUALITY CALCULATIONS. STORM WATER CALS MUST BE
 APPROVED FROM 100045TH STREET ENGINEERING SERVICES.
 7. PLEASE SHOW ON DRAWINGS THE POLLUTION PREVENTION
 PLAN SHOWING SILT FENCE AROUND THE SITE & CATCH BASINS
 DURING CONSTRUCTION AND ALL DEMOLITION PHASE.HEIGHT
 OF FENCE SHOULD BE HIGH ENOUGH PER FDEP TO STOP DUST
 PARTICLES.
 8. WATER & SEWER PLANS MUST BE APPROVED FROM 45TH
 STREET (MANNY G.), UTILITY DEPT BEFORE WE APPROVED.
 9. YOUR PLANS NOT ORIGINALLY SIGNED & SEALED.PLANS
 MUST BE SEAL & SIGNED BY FLORIDA P.E.
  
 PLEASE RESPOND EACH ITEM IN DETAIL TO EXPEDITE YOUR
 PERMITTING PROCESS
  