Plan Review Notes
Plan Review Notes For Permit 07110067
Permit Number 07110067
Review Stop B
Sequence Number 1
Notes
Date Text
2007-11-16 14:27:242004 FBC W/2007 REVISIONS
 INSTALL WALL MOUNTED ILLUMINATED BOXSIGN
  
 DENIED BY BUILDING
  
 1) TWO COPIES OF ALL PLANS/DRAWINGS ARE REQUIRED. SEE
 FBC* 106.1 CITY AMENDMENTS.
  
 2) SUBMIT SIGNED AND SEALED ENGINEERING DETAILS FOR THE
 ATTACHMENT OF THE SIGN TO THE STRUCTURE. SPECIFY THE
 FASTENERS,FASTENER SPACING, ETC. SPECIFY THE WIND
 DESIGN CRITERIA ON THE PLANS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]