Plan Review Notes For Permit 07110020 |
Permit Number |
07110020 |
|
Review Stop |
E |
Sequence Number |
4 |
|
Notes |
Date |
Text |
2008-06-12 13:36:44 | ** DENIED REVISION ** | | | | 1) NOTE: PLEASE SEE TABLE 13-415.2.C WHICH ALLOWS 1.0 | | WATTS PER SQ FT. AS THE ZONE IS SHOWN AS 691 SQ FT, HOW | | CAN THE LIGHTING BE SHOWN AS 752WATTS FOR DESIGN WHEN | | THE CODE GIVES A MAXIMUM OF 1.0 PER SQ FT WHICH | | 691WATTS? | | | | ** IMPORTANT** | | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP | | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE | | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. | | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. | | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY | | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, | | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO | | TWO SETS/FOLDERS/BINDERS ETC. | | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS | | SHOULD BE SUBMITTED FOR REFERENCE. | | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID | | ANY DELAYS. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. IF | | THERE ARE ANY QUESTIONS OR COMMENTS PLEASE DO NOT | | HESITATE IN CONTACTING THIS OFFICE. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW II | | CONSTRUCTION SERVICES DEPARTMENT | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] |
|