Plan Review Notes
Plan Review Notes For Permit 07110020
Permit Number 07110020
Review Stop E
Sequence Number 4
Notes
Date Text
2008-06-12 13:36:44** DENIED REVISION **
  
 1) NOTE: PLEASE SEE TABLE 13-415.2.C WHICH ALLOWS 1.0
 WATTS PER SQ FT. AS THE ZONE IS SHOWN AS 691 SQ FT, HOW
 CAN THE LIGHTING BE SHOWN AS 752WATTS FOR DESIGN WHEN
 THE CODE GIVES A MAXIMUM OF 1.0 PER SQ FT WHICH
 691WATTS?
  