2008-02-11 16:26:41REVIEW #: 2ND
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH
 PREVIOUS REVIEW COMMENTS AS WELL AS DESIGNER'S WRITTEN
 RESPONSES FOR THE PURPOSE OF CONTINUITY.
  
 1. THE THROUGH-PENETRATION FIRESTOP SYSTEMS SHOWN ON
 PLANS DO NOT ALLOW FOR INSULATED PIPE. AS THIS WILL
 INVOLVE INSULATED REFRIGERANT PIPE, THIS SPECIFIED
 SYSTEMS ARE NOT APPROPRIATE. PLEASE PROVIDE A
 THOUGH-PENETRATION FIRESTOP SYSTEM WHICH IS APPROPRIATE
 FOR TH TYPE OF PENETRATIONS BEING POTECTED IN
 ACCORDANCE WITH FBC 712.3.
  
 2 AND 3: OK
  