Plan Review Notes For Permit 07110020 |
Permit Number |
07110020 |
|
Review Stop |
M |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2008-02-11 16:26:41 | REVIEW #: 2ND | | ACTION: DENIED | | | | FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS | | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH | | | | THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH | | PREVIOUS REVIEW COMMENTS AS WELL AS DESIGNER'S WRITTEN | | RESPONSES FOR THE PURPOSE OF CONTINUITY. | | | | 1. THE THROUGH-PENETRATION FIRESTOP SYSTEMS SHOWN ON | | PLANS DO NOT ALLOW FOR INSULATED PIPE. AS THIS WILL | | INVOLVE INSULATED REFRIGERANT PIPE, THIS SPECIFIED | | SYSTEMS ARE NOT APPROPRIATE. PLEASE PROVIDE A | | THOUGH-PENETRATION FIRESTOP SYSTEM WHICH IS APPROPRIATE | | FOR TH TYPE OF PENETRATIONS BEING POTECTED IN | | ACCORDANCE WITH FBC 712.3. | | | | 2 AND 3: OK | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | RONALD J. REGUEIRO | | 561.805.6719 | | [email protected] | | |
|