2007-11-28 19:19:35REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 AMENDMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. M-2: KEY NOTE #10, ARE REFRIGERANT LINES PENETRATING
 RATED FLOOR/CEILING ASSEMBLIES TO GET TO ROOF? IF SO,
 PROVIDE DETAIL FOR THROUGH-PENETRATION FIRESTOP SYSTEM
 IN COMPLIANCE WITH FBC 712.4.1.2.
  
 2. ALL RECONFIGURED SPACES INTENDED FOR OCCUPANCY SHALL
 BE PROVIDED WITH NATURAL OR MECHANICAL VENTILATION OR
 EXHAUST IN ACCORDANCE WITH FBC, M CHAPTER 4 PER THE
 REQUIREMENTS OF FBC, EB 609.1. PROVIDE OUTSIDE AIR
 CALCULATIONS SHOWING VENTILATION REQUIREMENTS INCLUDING
 OCCUPANCY CLASSIFICATION, OCCUPANT LOAD, CFM REQUIRED
 AND CFM PROVIDED IN ACCORDANCE WITH FBC, M TABLE
 403.3.
  
 3. M-3: PRE-ENGINEERED A/C STANDS ARE DEFINED AS
 STRUCTURAL COMPONENTS UNDER FAC RULE 9B-72 AND AS SUCH
 A PRODUCT APPROVAL IS REQUIRED. PROVIDE A PRODUCT
 APPROVAL FOR THE SPECIFIC STAND TO BE INSTALLED ALONG
 WITH INSTALLATION INSTRUCTIONS. THE STAND IS TO BE
 SECURED TO THE STRUCTURE AND THE CONDENSING UNIT IS TO
 BE ATTACHED TO THE STAND PER THE INSTRUCTIONS.
  