Plan Review Notes For Permit 07110020 |
Permit Number |
07110020 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2007-11-28 16:39:36 | ** DENIED** | | | | | | 1) NOTE: PLEASE PROVIDE LIGHTING PERFORMANCE/DENSITIES | | PER 13-415.2.B.1, TABLE 13-415.2.B | | | | 2) NOTE: PLEASE CLARIFY IT ROOM SHOWN ON PLANS, IF THIS | | IS A TRUE IT ROOM PER NEC 645, PLEASE PROVIDE | | INFORMATION ON DISCONNECTING MEANS AS REQUIRED PER | | 645.10. IF THIS IS NOT AN IT ROOM, PLEASE CHANGE | | DESIGNATION ON PLANS. | | PLEASE SEE NEC 645 SCOPE, AND NFPA-75 CHAPTERS 4 AND | | 5. | | | | *** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY | | COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE | | DO NOT HESITATE IN CONTACTING THIS OFFICE. | | PLEASE SEE BELOW FOR CONTACT INFORMATION. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW II | | CONSTRUCTION SERVICES DEPT. | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] | | | | | | | | |
|