Plan Review Notes
Plan Review Notes For Permit 07110020
Permit Number 07110020
Review Stop E
Sequence Number 1
Notes
Date Text
2007-11-28 16:39:36** DENIED**
  
  
 1) NOTE: PLEASE PROVIDE LIGHTING PERFORMANCE/DENSITIES
 PER 13-415.2.B.1, TABLE 13-415.2.B
  
 2) NOTE: PLEASE CLARIFY IT ROOM SHOWN ON PLANS, IF THIS
 IS A TRUE IT ROOM PER NEC 645, PLEASE PROVIDE
 INFORMATION ON DISCONNECTING MEANS AS REQUIRED PER
 645.10. IF THIS IS NOT AN IT ROOM, PLEASE CHANGE
 DESIGNATION ON PLANS.
 PLEASE SEE NEC 645 SCOPE, AND NFPA-75 CHAPTERS 4 AND
 5.
  
 *** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  