Plan Review Notes
Plan Review Notes For Permit 07100863
Permit Number 07100863
Review Stop M
Sequence Number 1
Notes
Date Text
2007-11-06 09:35:33PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) SHOW COMPLYANCE WITH 2004 FBC/M 502.3
 BATTERY-CHARGING AREAS. VENTILATION SHALL BE PROVIDED
 IN AN APPROVED MANNER IN BATTERY-CHARGING AREAS TO
 PREVENT A DANGEROUS ACCUMULATION OF FLAMMABLE GASES.
 502.4 STATIONARY LEAD-ACID BATTERY SYSTEMS. VENTILATION
 SHALL BE PROVIDED FOR STATIONARY LEAD-ACID BATTERY
 SYSTEMS IN ACCORDANCE WITH THIS CHAPTER AND SECTION
 502.4.1 OR 502.4.2.
 502.4.1 HYDROGEN LIMIT. THE VENTILATION SYSTEM
 SHALL BE DESIGNED TO LIMIT THE MAXIMUM CONCENTRATION OF
 HYDROGEN TO 1.0 PERCENT OF THE TOTAL VOLUME OF THE
 ROOM.
 502.4.2 VENTILATION RATE. CONTINUOUS VENTILATION
 SHALL BE PROVIDED AT A RATE OF NOT LESS THAN 1 CUBIC
 FOOT PER MINUTE PER SQUARE FOOT (CFM/FT 2 ) [0.00508 M
 3 /(S.M 2)] OF FLOOR AREA OF THE ROOM.
 502.5 VALVE-REGULATED LEAD-ACID BATTERIES.
 VALVE-REGULATED LEAD-ACID BATTERY SYSTEMS AS REGULATED
 BY THE FLORIDA FIRE PREVENTION CODE , SHALL BE PROVIDED
 WITH VENTILATION IN ACCORDANCE WITH SECTION 502.5.1 OR
 502.5.2 FOR ROOMS AND IN ACCORDANCE WITH SECTION
 502.5.3 OR 502.5.4 FOR CABINETS.
  