 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING:
  
 1} INDICATE PANEL DESIGNATION AND CIRCUIT NUMBERS,
 CONDUIT AND CONDUCTOR SIZE AND TYPE, AND THE LOCATION
 FOR EQUIPMENT BEING WIRED UNDER THIS PERMIT.
  
 2} ALL PLANS SUBMITTED FOR REVIEW MUST HAVE A CITY
 PLACE STAMP. 106.1.3
  
 3} PLEASE SUBMIT A FLOOR PLAN AND INDICATING THE
 LOCATION OF ALL EQUIPMENT AND DEVICES BEING INSTALLED
 UNDER THE SCOPE OF THIS APPLICATION.106.1.1 FBC. THERE
 ARE SEVERAL SHEETS SUBMITTED WITH THE APPLICATION, NONE
 OF WHICH SEEM TO BE RELEVANT TO THE DESCRIPTION ON THE
 APPLICATION.
  
 4} THE PERSON SEALING THE DOCUMENT MUST ALSO PRINT HIS
 NAME IN THE TITLE BLOCK PER 61G1-16.004 FAC.
  
 5} THE ARCHITECTURAL FIRM MUST DISPLAY THE CERTIFICATE
 OF AUTHORIZATION ON THE TITLE BLOCK PER 481.221 (8).
  
 PLEASE INDICATE THE CODE CYCLES THIS PROJECT WAS
 DESIGNED UNDER. 2004 FBC, 2005 NEC ETC. ADD TO NOTES
 FOR CLARITY IN THE FIELD AND COMPLIANCE WITH 106.1.3
 FBC AS AMENDED.
  