2008-01-15 10:50:46 | ****CORRECTIONS**** |
| |
| SAMANTHA HILL, BUILDING PLANS EXAMINER |
| 561-805-6724 [email protected] |
| |
| FBCFLORIDA BUILDING CODE 2004 |
| FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING |
| CODE |
| FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC* |
| CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 |
| |
| FAC FLORIDA ADMINISTRATIVE CODE |
| FSFLORIDA STATUTE |
| |
| 1.THE MIAMIDADE NOA PROVIDED IS INCOMPLETE AND IS |
| ILLEGIBLE.PRODUCT APPROVALS MAY BE AVAILABLE AT |
| WWW.BUILDINGCODEONLINE.COM OR WWW.FLORIDABUILDING.ORG. |
| |
| 2.THE ANCHOR PROPOSED IS NOT INCLUDED IN THE PRODUCT |
| APPROVAL PROVIDED, WEATHERGUARD BUILDING PRODUCTS. SPEC |
| SHEETS WERE PROVIDED BUT THEY ARE FOR A DIFFERENT |
| PRODUCT, POMA CORPORATION.SEE PAGE 4 OF 5 OF THE |
| PRODUCT APPROVAL.THE INSTALLATION SCHEDULE REFERS TO |
| A WINDOW PRODUCT APPROVAL.IT IS NOT CLEAR WHAT |
| PRODUCT YOU ARE INSTALLING; THEREFORE, CODE COMPLIANCE |
| CANNOT BE DETERMINED. |
| |
| 3.SEE SHEET 4.SOME ANCHORS ARE NOT PERMITTED FOR |
| THE WEATHERGUARD PRODUCT INTO A CONCRETE BLOCK |
| SUBSTRATE.ANCHOR SPACING SHOULD BE COMPLIANT WITH |
| THIS SHEET, NOT WITH A SPEC SHEET FROM ANOTHER |
| PRODUCT. |
| |
| 4.WHEN REFERRING TO THE SHUTTER CONNECTION MOUNTING |
| TYPE, COLUMN 4, PLASE REFER TO C1 THROUGH C5 TO |
| CORRELATE WITH THE ANCHOR SCHEDULE.IT APPEARS THAT |
| YOU ARE USING A C1 CONNECTION; THEREFORE, "C1" SHOULD |
| BE STATED AS THIS COLUMN (RATHER THAN "WALL MOUNT"). |
| |
| 5.ANCHOR SIZE ON TH CHART IS NOTED AS 7/8" IN LENGTH. |
| PLEASE NOTE THAT THIS IS AN EMBEDMENT REQUIREMENT; |
| THEREFORE AN ANCHOR OF THIS LENGTH WILL NOT MEET THE |
| EMBEDMENT REQUIREMENT IF THE BUILDING HAS STUCCO. |
| |