2008-01-15 10:50:46****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.THE MIAMIDADE NOA PROVIDED IS INCOMPLETE AND IS
 ILLEGIBLE.PRODUCT APPROVALS MAY BE AVAILABLE AT
 WWW.BUILDINGCODEONLINE.COM OR WWW.FLORIDABUILDING.ORG.
  
 2.THE ANCHOR PROPOSED IS NOT INCLUDED IN THE PRODUCT
 APPROVAL PROVIDED, WEATHERGUARD BUILDING PRODUCTS. SPEC
 SHEETS WERE PROVIDED BUT THEY ARE FOR A DIFFERENT
 PRODUCT, POMA CORPORATION.SEE PAGE 4 OF 5 OF THE
 PRODUCT APPROVAL.THE INSTALLATION SCHEDULE REFERS TO
 A WINDOW PRODUCT APPROVAL.IT IS NOT CLEAR WHAT
 PRODUCT YOU ARE INSTALLING; THEREFORE, CODE COMPLIANCE
 CANNOT BE DETERMINED.
  
 3.SEE SHEET 4.SOME ANCHORS ARE NOT PERMITTED FOR
 THE WEATHERGUARD PRODUCT INTO A CONCRETE BLOCK
 SUBSTRATE.ANCHOR SPACING SHOULD BE COMPLIANT WITH
 THIS SHEET, NOT WITH A SPEC SHEET FROM ANOTHER
 PRODUCT.
  
 4.WHEN REFERRING TO THE SHUTTER CONNECTION MOUNTING
 TYPE, COLUMN 4, PLASE REFER TO C1 THROUGH C5 TO
 CORRELATE WITH THE ANCHOR SCHEDULE.IT APPEARS THAT
 YOU ARE USING A C1 CONNECTION; THEREFORE, "C1" SHOULD
 BE STATED AS THIS COLUMN (RATHER THAN "WALL MOUNT").
  
 5.ANCHOR SIZE ON TH CHART IS NOTED AS 7/8" IN LENGTH.
 PLEASE NOTE THAT THIS IS AN EMBEDMENT REQUIREMENT;
 THEREFORE AN ANCHOR OF THIS LENGTH WILL NOT MEET THE
 EMBEDMENT REQUIREMENT IF THE BUILDING HAS STUCCO.
  