2007-12-28 15:47:02 | ****CORRECTIONS**** |
| |
| SAMANTHA HILL, BUILDING PLANS EXAMINER |
| 561-805-6724 [email protected] |
| |
| FBCFLORIDA BUILDING CODE 2004 |
| FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING |
| CODE |
| FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL |
| FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 |
| |
| FAC FLORIDA ADMINISTRATIVE CODE |
| FSFLORIDA STATUTE |
| |
| |
| 1.THE VALUE OF THE JOB IS TO INCLUDE LABOR (NOTE THAT |
| FEES ARE CHARGED BASED ON VALUE, NOT COST).$4800 HAS |
| BEEN ADDED AS A LABOR COST TO REMOVE AND INSTALL 16 |
| WINDOWS, INSTALL 16 SHUTTERS. |
| |
| 2.PLEASE KEEP THE PRESTORM PREPARATION PLAN IN THE |
| PERMIT PACKAGE (REQUIRED FOR PERMIT ISSUANCE). |
| |
| 3.ALL CHANGES TO THE PLAN ARE TO BE CLOUDED AND |
| MARKED WITH A REVISION NUMBER.FAILURE TO DO THIS |
| CAUSES FURTHER DELAYS.SEE CORRECTION #4. |
| |
| 4.SOME WINDOWS HAVE NOW BEEN MARKED "EXISTING |
| EGRESS".IT IS NOT CLEAR WHY THIS LANGUAGE HAS BEEN |
| ADDED; IT DOES NOT APPEAR ON THE PLAN DATED 12/6/07. |
| THE WINDOWS DO NOT COMPLY WITH EMERGENCY EGRESS |
| REQUIREMENTS APPLICABLE TO DAY CARE ROOMS.THE |
| RESPONSE LETTER STATES THAT EMERGENCY EGRESS IS NOT |
| REQUIRED.WHY HAS THE PLAN BEEN REVISED IN THIS WAY? |
| |
| ALSO, THIS CHANGE HAS NOT BEEN CLOUDED.HAS ANYTHING |
| ELSE ON THE PLAN BEEN REVISED AND NOT SHOWN AS A |
| REVISION?PLEASE REMOVE THIS LANGUAGE FROM THE PLAN OR |
| REVISE THE PLAN TO COMPLY WITH EGRESS REQUIREMENTS. |
| |
| 5.THE SCOPE OF WORK IS NOT CLEAR.THE APPLICATION |
| STATES "REMOVAL & INSTALLATION OF 11 WINDOWS".WINDOWS |
| ARE MARKED 1, 2, "EXISTING EGRESS" OR "EXISTING".THE |
| SHUTTER INSTALLATION SCHEDULE INCLUDES INFORMATION FOR |
| OPENING TYPES 1 AND 2. |
| |
| A.REVISE INSTALLATION SCHEDULE TO CORRELATE WITH EACH |
| OPENING.YOU MAY USE ONE LINE FOR SEVERAL OPENINGS BUT |
| THE INFORMATION MUST BE CORRECT.THE OPENING SIZE ON |
| THE INSTALLATION SCHEDULE SHOULD BE THE OPENING SIZE, |
| NOT THE WINDOW SIZE. |
| |
| B.AREN'T THE WINDOWS IN OPENINGS "EXISTING EGRESS" |
| AND "EXISTING" BEING REPLACED?SHUTTERS OVER THESE |
| WINDOWS WAS AN ISSUE IN PREVIOUS PLAN REVIEWS, BUT THE |
| PLAN NOW DOESN'T SHOW THEM AS HAVING SHUTTERS |
| INSTALLED.CLARIFY WHICH WINDOWS ARE BEING REPLACED, |
| WHICH OPENINGS WILL HAVE SHUTTERS INSTALLED. |
| |
| C.APPLICATION STATES 11 WINDOWS;PLAN SHOWS 16 |
| WINDOWS, 7 OPENINGS.THE PLAN SHOWS A LOT OF |
| INFORMATION WHICH IS NOT REQUIRED, YET DOES NOT INCLUDE |
| THE INFORMATION REQUIRED FOR PERMIT ISSUANCE.THE |
| PERMIT APPLICATION SHOULD BE CONSISTENT WITH THE SCOPE |
| OF WORK AND THE PLAN.PLEASE REVISE. |
| |
| 6.FOR THE WINDOWS, SHUTTERS, AND MULLIONS, THE |
| FOLLOWING IS REQUIRED: |
| |
| A.FLORIDA STATE OR LOCAL PRODUCT APPROVAL, |
| WWW.FLORIDABUILDING.ORG |
| |
| B.EVALUATION REPORT |
| |
| C.INSTALLATION INSTRUCTIONS |
| |
| PREVIOUSLY, A MIAMIDADE NOA WAS SUBMITTED.NOAS |
| INCLUDE THE EVALUATION REPORT AND THE INSTALLATION |
| INSTRUCTIONS IN ONE DOCUMENT.HOWEVER, FLORIDA STATE |
| PRODUCT APPROVAL WAS NOT SUBMITTED.NOW, ONLY |
| MIAMIDADE NOA FOR THE SINGLE HUNG WINDOW HAS BEEN |
| PROVIDED ALONG WITH TWO COPIES OF THE FLORIDA STATE |
| PRODUCT APPROVAL, A SPEC SHEET FOR THE SHUTTERS (NO |
| PRODUCT APPROVAL), AND NOTHING FOR THE MULLIONS. |
| PLEASE PROVIDE ALL REQUIRED PAPERWORK FOR EACH ITEM; |
| TWO SETS. |
| |
| |
| |
| |
| |